GE Multilin F650 Digital Bay Controller 2-13
2 PRODUCT DESCRIPTION 2.4 TECHNICAL SPECIFICATIONS
2
t) AUXILIARY UNDERVOLTAGE (27X)
u) UNDERFREQUENCY (81U)
v) OVERFREQUENCY (81O)
Level accuracy
îČ1% reading îČ0.1% Full Scale from 10 to 275 V
Trip delay 0.00 to 900.00 s. in steps of 0.01 s
Reset delay 0.00 to 900.00 s. in steps of 0.01 s
Timing accuracy ±3.5% of operate time or 30 ms. (whichever is greater)
Snapshot Events Selectable by setting
Voltage Input Fundamental Phasor
Pickup level 3 to 300 V in steps of 1 V
Reset level 97% of the pickup level
Level accuracy
îČ1% reading îČ0.1% Full Scale from 10 to 275 V
Curve Shapes Fixed time or inverse curve
Reset type Instantaneous
Curve Multiplier (Time Dial) 0.00 to 900.00 s. in steps of 0.01 s
Timing accuracy ±3.5% of operate time or 30 ms. (whichever is greater)
Snapshot Events Selectable by setting
Pickup level 20.00 to 65.00 Hz in steps of 0.01 Hz
Reset level Pickup + 0.03 Hz
Level accuracy
îČ0.01 Hz of the reading
Trip delay 0.00 to 900.00 s. in steps of 0.01 s
Reset delay 0.00 to 900.00 s. in steps of 0.01 s
Minimum voltage threshold 30 to 300V in steps of 1 V
Timing accuracy ±3.5% of operate time or 100 ms. (whichever is greater)
Snapshot Events Selectable by setting
Pickup level 20.00 to 65.00 Hz in steps of 0.01 Hz
Reset level Pickup - 0.03 Hz
Level accuracy
îČ0.01 Hz of the reading
Trip delay 0.00 to 900.00 s. in steps of 0.01 s
Reset delay 0.00 to 900.00 s. in steps of 0.01 s
Minimum voltage threshold 30 to 300V in steps of 1 V
Timing accuracy ±3.5% of operate time or 100 ms. (whichever is greater)
Snapshot Events Selectable by setting