EasyManuals Logo

GE Multilin GEK-113000T User Manual

GE Multilin GEK-113000T
533 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #175 background imageLoading...
Page #175 background image
5-34 F650 Digital Bay Controller GE Multilin
5.4 PROTECTION ELEMENTS 5 SETPOINTS
5
5.4.2.4 ANSI CURVES
This family of curves complies with American Standard ANSI C37.90 for Extremely inverse, Very inverse, Normally inverse
and Moderately inverse curves. The formulas that define these curves are as follows:
where:
T = Operation time (in seconds).
Dial = Multiplying factor
I = Input current
I
pickup
= Current pickup setpoint
A, B, C, D, E = Constants
T
reset
= Reset time (in seconds) assuming a 100% of power capacity and that the reset is activated
T
r
= Characteristic constant
The different constants that define the above-mentioned curves are:
Table 5–34: CONSTANTS FOR ANSI CURVES
ANSI CURVE SHAPE A B C D E TR
ANSI Extremely Inverse 0.0399 0.2294 0.5 3.0094 0.7222 5.67
ANSI Very Inverse 0.0615 0.7989 0.34 -0.284 4.0505 3.88
ANSI Normally Inverse 0.0274 2.2614 0.3 -4.1899 9.1272 5.95
ANSI Moderately Inverse 0.1735 0.6791 0.8 -0.08 0.1271 1.08
TDialA
B
I
I
pickkup
-------------------
C–
îšč

-----------------------------------
D
I
I
pickup
----------------
C–
îšč

2
-----------------------------------
E
I
I
pickup
----------------
C–
îšč

3
-----------------------------------
+++=
T
RESET
TDM
T
r
I
I
pickup
----------------
îšč

2
1–
----------------------------------
î™”=

Table of Contents

Other manuals for GE Multilin GEK-113000T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Multilin GEK-113000T and is the answer not in the manual?

GE Multilin GEK-113000T Specifications

General IconGeneral
BrandGE
ModelMultilin GEK-113000T
CategoryController
LanguageEnglish

Related product manuals