GE Multilin F650 Digital Bay Controller 5-39
5 SETPOINTS 5.4 PROTECTION ELEMENTS
5
Table 5–38: 51PH/51PL UNIT SETPOINTS
If the voltage restraint feature is disabled, the pickup level always remains at the value set in the Pickup Level setpoint.
The snapshot event setpoint enables or disables the snapshot event generation for the phase time overcurrent units.
SETPOINT > PROTECTION ELEMENTS > PHASE CURRENT >
> PHASE TOC HIGH > PHASE TOC HIGH 1> PHASE TOC HIGH 2 > PHASE TOC HIGH 3
> PHASE TOC LOW > PHASE TOC LOW 1 > PHASE TOC LOW 2 > PHASE TOC LOW 3
SETPOINT DESCRIPTION NAME DEFAULT VALUE STEP RANGE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Input type Input PHASOR(DFT) N/A [PHASOR – RMS]
Pickup level Pickup Level 1.00 0.01 A [0.05 : 160.00]
Curve shape Curve IEEE Ext Inv N/A [See list of curves]
Time Dial TD Multiplier 1.00 0.01 s [0.00 : 900.00]
Reset type Reset INSTANTANEOUS N/A [INSTANTANEOUS – LINEAR]
Voltage Restraint Voltage Restraint DISABLED N/A [DISABLED – ENABLED]
Snapshot Event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]

Table of Contents

Other manuals for GE Multilin GEK-113000T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Multilin GEK-113000T and is the answer not in the manual?

GE Multilin GEK-113000T Specifications

General IconGeneral
BrandGE
ModelMultilin GEK-113000T
CategoryController
LanguageEnglish

Related product manuals