GEK-113000T F650 Digital Bay Controller C-13
APPENDIX C C.1 FACTORY DEFAULT SETTINGS
C
SETPOINT > PROTECTION ELEMENTS >VOLTAGE ELEMENTS>AUXILIARY OV
AUXILIARY OV 1> AUXILIARY OV 2 > AUXILIARY OV 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Pickup Level Pickup Level 10 1 V [3 : 300]
Trip Time Trip Delay 10.00 0.01 s [0.00 : 900.00]]
Reset Time Reset Delay 0.00 0.01 s [0.00 : 900.00]
Snapshot Event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > PROTECTION ELEMENTS >VOLTAGE ELEMENTS>AUXILIARY UV
AUXILIARY UV 1> AUXILIARY UV 2 > AUXILIARY UV 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Pickup Level Pickup Level 10 1 V [3 : 300]
Curve shape Curve DEFINITE TIME N/A
[DEFINITE TIME –
INVERSE TIME]
Time Dial Delay 10.00 0.01 s [0.00 : 900.00]
Snapshot Event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > PROTECTION ELEMENTS > POWER > FORWARD POWER
FORWARD POWER 1> FORWARD POWER 2 > FORWARD POWER 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Block from off-line Blk Time After Close 0.00 0.01 s [0.00 : 900.00]
Pickup level for stage 1 Stage 1 Tap 10.00 0.01MW [0.00 : 10000.00]
Trip time for stage 1 Stage 1 Time 60.00 0.01 s [0.00 : 900.00]
Pickup level for stage 2 Stage 2 Tap 20.00 0.01MW [0.00 : 10000.00]
Trip time for stage 2 Stage 2 Time 60.00 0.01 s [0.00 : 900.00]
Snapshot Event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]