GE Multilin F650 Digital Bay Controller 2-11
2 PRODUCT DESCRIPTION 2.4 TECHNICAL SPECIFICATIONS
2
m) SENSITIVE GROUND DIRECTIONAL (67SG)
n) THERMAL MODEL (49)
o) PHASE OVERVOLTAGE (59P)
Angle accuracy
îČ2Âș for I>0.1 A and V>5 Vac
Operate time <30ms, typically
Directionality Forward and reverse selectable by setting
Polarizing Voltage
Polarizing Voltage V
N
(measured or calculated, selected by setting)
Operating Current
Isg (measured from 5
th
current transformer)
Polarizing Voltage threshold 0 to 300 Vac in steps of 1 V
Characteristic angle -90Âș to +90Âș in steps of 1Âș
Block Logic Permission or Block selectable by setting
Angle accuracy
îČ2Âș for I>0.1 A and V>5 Vac
Operate time <30ms, typically
Current Input Fundamental Phasor (without harmonics)
Rated current For connection to 1 or 5 A CTs.
Pickup level 0.05 to 160.0 A in steps of 0.01 A
Reset level 97% of the pickup level
Level Accuracy
îČ0.5% of the reading îČ 10 mA from 0.05 to 10 A
îČ1.5% of the reading for higher values
Timing accuracy ±3.5% of operate time or 30 ms. (whichever is greater)
Heating constant Between 3 and 600 minutes
Cooling constant 1 to 6 times the heating constant
Snapshot Events Selectable by setting
Voltage Input Fundamental Phasor (without harmonics) of phase-to-phase
voltages
Pickup level 3 to 300 in steps of 1 V
Reset level 97% of the pickup level
Level Accuracy
îČ1% reading îČ0.1% Full Scale from 10 to 275 V
Trip delay 0.00 to 900.00 s. in steps of 0.01 s.
Reset delay 0.00 to 900.00 s. in steps of 0.01 s.
Timing accuracy ±3.5% of operate time or 30 ms. (whichever is greater)
Logic Any/Two/All phases logic selectable by setting
Snapshot Events Selectable by setting