EasyManuals Logo

GE Multilin GEK-113000T User Manual

GE Multilin GEK-113000T
533 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
GE Multilin F650 Digital Bay Controller 2-19
2 PRODUCT DESCRIPTION 2.4 TECHNICAL SPECIFICATIONS
2
2.4.4 USER –PROGRAMABLE ELEMENTS
a) PLC LOGIC
b) FLEXCURVES
c) USER-PROGRAMMABLE LEDS
d) USER-DEFINABLE DISPLAYS
Programming language: The logical configuration is performed using graphical functions based on the
IEC 61131-3 standard.
Lines of code: 512
Supported operations: NOT, XOR, OR (2 to 8 inputs), AND (2 to 8 inputs), NOR (2 to 8 inputs),
NAND (2 to 8 inputs), Latch (Reset Dominant), Edge Detectors, Timers.
2 inputs default gates, from 3 to 8 inputs provided in library format.
Libraries: Logical gates fully programmable by user. To create user-programmable logic to
be distributed as a single object.
Inputs: Any logical variable, contact or virtual input
Number of timers: 8 maximum in each logic scheme (provided in library format)
Number: 4 (A through D)
Reset points: 40 (0 through 1 of pickup)
Operate points: 80 (1 through 20 of pickup)
Time delay: 0 to 65535 ms in steps of 1
Saturation Level 20 times the pickup level
Number: 15 configurable LEDs plus a ready non configurable LED
Programmability: from any logical variable, contact, or virtual input
Reset mode: Self-reset or Latched.
The first 5 LED’s are latched by hardware (red color ones), usually configured for
trip signals.
The following 10 ones (yellow and green) are self-reset but can be latched
through PLC configuration.
Reset Signal: The LED’s can be reset by hardware, pressing the front “esc” key during more
than 3 seconds or using the LED reset signal through PLC configuration.
Number of configurable displays: 1 (one line diagram fully configurable). In graphical displays only
Number of fixed displays: 6, Metering (in primary values), Snapshot events (all and new), Alarms, Inputs
and outputs screen with test functionality for inputs and outputs. In graphical dis-
plays only
Number of selectable displays: Logotype, metering or both in scrolling mode, can be selectable as default
screen in text display for all models (basic and mimic). The metering screen con-
tains current and voltages for phases and ground in primary values.

Table of Contents

Other manuals for GE Multilin GEK-113000T