Password protected window for Earth Fault 1 i.e. IN1>1 Function, IN1>2
Function and IN1>3 Function. The functions can be set as Disabled / DT
/ IDMT.
Note: Setting will be seen only when it is enabled in Configuration
setting.
Password protected window for Earth Fault 2 i.e. IN2>1 Function, IN2>2
Function and IN2>3 Function. The functions can be set as Disabled / DT
/ IDMT.
Note: Setting will be seen only when it is enabled in Configuration
setting.
Password protected window for Thermal Overload i.e. Inh.Trip Dur ST,
K Coefficient, Thermal Trip, Thermal Alarm, Thermal Const. T1, Thermal
Const. T2, Cooling Const. Tr, Thermal Lockout and K.
Note: Setting will be seen only when it is enabled in Configuration
setting.
LOSS OF LOAD
Password protected window for Loss of Load
Enabled/Disabled, I<1 Current Set, I<1 Time Delay, T inhib.
Note: Setting will be seen only when it is enabled in Configuration
setting.
Password protected window for CB FAIL i.e. CB Fail Status, CB Fail
Timer, CBF Reset, CB Fail Timer, I<, IN<, Remove I> Start and Remove
IN> Start.
Note: Setting will be seen only when it is enabled in Configuration
setting.
Password protected window for Stall Detection i.e. Start Criteria,
Prolonged Start, (Starting Current and Prol. Start Time) Stall Rotor Strt
and Stall Detection (Stall setting and Stall time).
Note: Setting will be seen only when it is enabled in Configuration
setting.
Password protected window for Limit NB Starts i.e. Hot Start Status,
Hot Start NB, Cold Start Stat, Cold Start NB,
T.Betw.St.Status, Time Betwn Start and Inhib. Strt Time
Note: Setting will be seen only when it is enabled in Configuration
setting.
Note: The Group 2 function for the setting System Configuration, Overcurrent, Negative Sequence
O/C, Earth Fault 1, Earth Fault 2, Thermal Overload, Loss of Load, CB Fail, Stall Detection and
Limit NB Starts are similar to Group 1.