5 Configuration
P253/EN M/C
5-59
Supervising Time
10 Mins
Editable setting
By using the (+ /5) or (- /6) key, the desired Supervising Time can be
set. The setting range is from 1 to 120 Mins step 1Min.
T.Betw.St.Status
Enabled
Editable setting
By using the (+ /5) or (- /6) key, T.Betw.St.Status is Enabled.
Time Betwe Start
20 Mins
Editable setting
By using the (+ /5) or (- /6) key, the desired Time Betwe Start can be
set. The setting range is from 1 Min to 120 Mins in steps of 1Min.
Inhib. Strt Time
10 Mins
Editable setting
By using the (+ /5) or (- /6) key, the desired Inhib. Strt Time can be
set. The setting range is from 1 to 120 Mins in steps of 1Min.
2.3.17 Group 2 Menu
2.3.17.1
Edit Settings
GROUP 2
Password protected window for “GROUP 2’’ settings:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, EARTH
FAULT 1, EARTH FAULT 2, THERMAL OVERLOAD, LOSS OF LOAD,
CB FAIL, STALL DETECTION and LIMITS NB STARTS.
Note: Group 2 setting will be seen only when it is enabled in
Configuration setting.
SYSTEM CONFIG
Password protected window for System Configuration
i.e. 2nd
Harmonic (Disabled/Enabled), 2nd Harmonic Threshold and I>lift 2H.
Note: Setting will be seen only when it is enabled in Configuration
setting.
OVERCURRENT
Password protected window for Overcurrent i.e. I>1 Function, I>2
Function and I>3 Function. The functions can be set as Disabled / DT /
IDMT.
Note: Setting will be seen only when it is enabled in Configuration
setting.
NEG SEQUENCE O/C
Password protected window for Negative Sequence O/C
i.e. I2>1
Function, I2>2 Function and I2>3 Function. The functions can be set as
Disabled / DT / IDMT.
Note: Setting will be seen only when it is enabled in Configuration
setting.