Cold Start Stat
Disabled
Editable setting
By using the (+ /5) or (- /6) key, Cold Start Stat is Disabled.
Supervising Time
10 Mins
Editable setting
By using the (+ /5) or (- /6) key, the desired Supervising Time can
be set. The setting range is from 1 to 120 Mins in steps of 1 Min.
T.Betw.St.Status
Disabled
By using the (+ /5) or (- /6) key, the desired T.Betw.St.Status is
Disabled.
Inhib. Strt Time
10 Mins
Editable setting
By using the (+ /5) or (- /6) key, the desired Inhib. Strt Time can be
set. The setting range is from 1 to 120 Mins in steps of 1 Min
2.3.16.11.2 Edit Settings (if settings are disabled)
GROUP 1
Password protected window for “GROUP 1’’ settings:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, EARTH
FAULT 1, EARTH FAULT 2, THERMAL OVERLOAD, LOSS OF LOAD,
CB FAIL, STALL DETECTION and LIMITS NB STARTS.
Password protected window for LIMIT NB STARTS i.e. Hot Start Status
(Enabled/Disabled), Hot Start NB, Cold Start Stat (Enabled/Disabled)
Cold Start NB, Supervising Time, T.Betw.St.Status (Enabled/Disabled)
Time Betwe Start and Inhib. Strt Time.
Hot Start Status
Enabled
Editable setting
By using the (+ /5) or (- /6) key, Hot Start Status is Enabled.
Hot Start NB
2
Editable setting
By using the (+ /5) or (- /6) key, the desired Hot Start NB can be set
The setting range is from 1 to 5 in steps of 1.
By using the (+ /5) or (- /6) key, Cold Start Stat is Enabled.
Cold Start NB
3
Editable setting
By using the (+ /5) or (- /6) key, the desired Cold Start NB can be
set. The setting range is from 1 to 5 in steps of 1.