EasyManua.ls Logo

GE P50 Agile P253 - Page 97

GE P50 Agile P253
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P50 Agile P253
5 Configuration
P253/EN M/C
5-57
Starting Current
5.0 A
Editable setting
By using the (+ /5) or (- /6) key, the desired Starting Current can be
set. The setting range is from 1.0In to 5.0In in steps of 0.1
Prol. Start Time
15.00 S
Editable setting
By using the (+ /5) or (- /6) key, the desired Prol. Start Time can be
set. The setting range is from 1.00s to 199s in steps of 0.01s
Stall Rotor Strt
Enabled
Editable setting
By using the (+ /5) or (- /6) key, Stall Rotor Start is Enabled.
Stall Detection
Enabled
Editable setting
By using the (+ /5) or (- /6) key, Stall Detection is Enabled.
Stall Setting
2.5 A
Editable setting
By using the (+ /5) or (- /6) key, the desired Stall Setting can be set.
The setting range is from 1 to 5 In in steps of 0.1 In
Stall Time
6.00 S
Editable setting
By using the (+ /5) or (- /6) key, the desired Stall Time can be set.
The setting range is from 1s to 199s in steps of 0.01s
2.3.16.11 Group1 –Limit Nb Starts Submenu
2.3.16.11.1 Edit Settings (if settings are disabled)
GROUP 1
Password protected window for “GROUP 1’’ setting i.e. SYSTEM
CONFIG, OVERCURRENT, NEG SEQUENCE O/C, EARTH FAULT 1,
EARTH FAULT 2, THERMAL OVERLOAD, LOSS OF LOAD, CB FAIL,
STALL DETECTION and LIMITS NB STARTS.
LIMIT NB STARTS
Password protected window for LIMIT NB STARTS i.e. Hot Start Status
(Enabled/Disabled), Hot Start NB, Cold Start Stat (Enabled/Disabled)
Cold Start NB, Supervising Time, T.Betw.St.Status (Enabled/Disabled)
Time Betwe Start and Inhib. Strt Time.
Hot Start Status
Disabled
Editable setting
By using the (+ /5) or (- /6) key, Hot Start Status is Disabled.

Table of Contents

Related product manuals