Password protected window for STALL DETECTION settings i.e. Start
Criteria, Prolonged Start (Enabled/Disabled), Starting Current, Prol. Start
Time, Stall Rotor Strt (Enabled/Disabled), Stall Detection
(Enabled/Disabled), Stall Setting and Stall Time.
Start Criteria
I
Editable setting
By using the (+ /5) or (- /6) key, the desired Status Criteria can be
set i.e. 52a / I / 52a+I
Prolonged Start
Disabled
Editable setting
By using the (+ /5) or (- /6) key, Prolonged Start is Disabled.
Stall Rotor Strt
Disabled
By using the (+ /5) or (- /6) key, Stall Rotor Start is Disabled.
Stall Detection
Disabled
Editable setting
By using the (+ /5) or (- /6) key, Stall Detection is Disabled.
2.3.16.10.2 Edit Settings (if settings are enabled)
GROUP 1
Password protected window for “GROUP 1’’ settings :
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, EARTH
FAULT 1, EARTH FAULT 2, THERMAL OVERLOAD, LOSS OF LOAD,
CB FAIL, STALL DETECTION and LIMITS NB STARTS.
Password protected window for STALL DETECTION settings i.e. Start
Criteria, Prolonged Start (Enabled/Disabled), Starting Current, Prol. Start
Time, Stall Rotor Strt (Enabled/Disabled), Stall Detection
(Enabled/Disabled), Stall Setting and Stall Time.
Start Criteria
I
Editable setting
By using the (+ /5) or (- /6) key, the desired Status Criteria can be
set i.e. 52a / I / 52a+I
Prolonged Start
Enabled
Editable setting
By using the (+ /5) or (- /6) key, Prolonged Start is Enabled.