9 SCADA Communications
P50 Agile P253
P253/EN M/C
OBJECT REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Number
Description
Function
Codes(dec)
Qualifier
Codes (hex)
Function
Codes (dec)
Qualifier
Codes (hex)
30
3
(default –
see note 1)
32-Bit Analog Input
without Flag
1(read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –
see note 2)
30
4
16-Bit Analog Input
without Flag
1(read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –
see note 2)
30
5
Single-precision,
floating-point with
flag
1(read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –
see note 2)
32
0
Analog Change
Event (Variation
0 is used to request
default variation)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
32
1
(default –
see note 1)
32-Bit Analog
Change Event
without Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
17, 28 (index)
32
2
16-Bit Analog
Change Event
without Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
17, 28 (index)
32
3
32-Bit Analog
Change Event with
Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
17, 28 (index)
32
4
16-Bit Analog
Change Event with
Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
17, 28 (index)
32
7
Single-precision,
floating-point with
time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
17, 28 (index)
50
0
Time and Date
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index
see note 2)
50
1(default –
see note 1)
Time and Date
1 (read)
2 (write)
00, 01 (start-stop)
06 (no range, or all)
07 (limited qty=1)
08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index
see note 2)
60
0
Class 0, 1, 2, and 3
Data
1 (read)
06 (no range, or all)
60
1
Class 0 Data
1 (read)
06 (no range, or all)
129 (response)
17,28
60
2
Class 1 Data
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
17,28
60
3
Class 2 Data
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
17,28
60
4
Class 3 Data
1(read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
17,28
80
1
Internal Indications
2 (write)
00 (start-stop)
(index must =7)
129 (response)
17,28
No Object (function
code only)
13 (cold restart)
No Object (function
code only)
14(warm restart)
No Object (function
code only)
23(delay meas.)

Table of Contents