P50 Agile P253
9 SCADA Communications
P253/EN M/C
9-21
OBJECT REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Number
Description
Function
Codes(dec)
Qualifier
Codes (hex)
Function
Codes (dec)
Qualifier
Codes (hex)
20
0
Binary Counter
(Variation 0 is
used to request
default variation)
1 (read)
7 (freeze)
8 (freezenoack)
9 (freeze clear)
10(frz. cl. Noack)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
20
1
32-Bit Binary
Counter
1 (read)
7 (freeze)
8 (freeze noack)
9 (freeze clear)
10(frz. cl. Noack)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –
see note 2)
20
2
16-Bit Binary
Counter
1 (read)
7 (freeze)
8 (freeze noack)
9 (freeze clear)
10 (frz.cl.Noack)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –
see note 2)
20
5
(default –
see note 1)
32-Bit Binary
Counter without
Flag
1 (read)
7 (freeze)
8 (freeze noack)
9 (freeze clear)
10 (frz.cl. Noack)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –
see note 2)
20
6
16-Bit Binary
Counter without
Flag
1 (read)
7 (freeze)
8 (freeze noack)
9 (freeze clear)
10 (frz. cl. Noack)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –
see note 2)
22
0
Counter change
Event
1 (read)
06 (no range, or all)
07, 08 (limited qty)
22
1 (default –
see note 1)
32-Bit Counter
Change Event
without Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
17, 28 (index –
see note 2)
22
2
16-Bit Counter
Change Event
without Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
17, 28 (index –
see note 2)
22
5
32-Bit Counter
Change Event with
Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
17, 28 (index –
see note 2)
22
6
16-Bit Counter
Change Event with
Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
17, 28 (index –
see note 2)
30
0
Analog Input
(Variation 0 is used
to request default
variation)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
30
1
32-Bit Analog Input
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –
see note 2)
30
2
16-Bit Analog Input
1(read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –
see note 2)