9 SCADA Communications
P253/EN M/C
9-21
OBJECT REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Number
Description
Function
Codes(dec)
Qualifier
Codes (hex)
Function
Codes (dec)
Qualifier
Codes (hex)
20
0
Binary Counter
(Variation 0 is
used to request
default variation)
1 (read)
7 (freeze)
8 (freezenoack)
9 (freeze clear)
10(frz. cl. Noack)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
20
1
32-Bit Binary
Counter
1 (read)
7 (freeze)
8 (freeze noack)
9 (freeze clear)
10(frz. cl. Noack)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –
see note 2)
20
2
16-Bit Binary
Counter
1 (read)
7 (freeze)
8 (freeze noack)
9 (freeze clear)
10 (frz.cl.Noack)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –
see note 2)
20
5
(default –
see note 1)
32-Bit Binary
Counter without
Flag
1 (read)
7 (freeze)
8 (freeze noack)
9 (freeze clear)
10 (frz.cl. Noack)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –
see note 2)
20
6
16-Bit Binary
Counter without
Flag
1 (read)
7 (freeze)
8 (freeze noack)
9 (freeze clear)
10 (frz. cl. Noack)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –
see note 2)
22
0
Counter change
Event
1 (read)
06 (no range, or all)
07, 08 (limited qty)
22
1 (default –
see note 1)
32-Bit Counter
Change Event
without Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
17, 28 (index –
see note 2)
22
2
16-Bit Counter
Change Event
without Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
17, 28 (index –
see note 2)
22
5
32-Bit Counter
Change Event with
Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
17, 28 (index –
see note 2)
22
6
16-Bit Counter
Change Event with
Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
17, 28 (index –
see note 2)
30
0
Analog Input
(Variation 0 is used
to request default
variation)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
30
1
32-Bit Analog Input
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –
see note 2)
30
2
16-Bit Analog Input
1(read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –
see note 2)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE P50 Agile P253 and is the answer not in the manual?

GE P50 Agile P253 Specifications

General IconGeneral
BrandGE
ModelP50 Agile P253
CategoryRelays
LanguageEnglish

Related product manuals