P50 Agile P253
13 Technical Specifications
P253/EN M/C
13-11
Peak acceleration after crossover Y 1 gn
No. of sweep cycles per axis 1
EUT condition
Energised
6.
Environmental tests
6.1 Dry heat test
IEC 60255-1,
IEC 60068-2-2: 2007
Bd
Start-up +20°C (EUT energised) Functional verification tests for 2 hours
Intermediate +40°C (EUT energised) Functional verification tests for 2 hours
High temp. claim +65°C (EUT
energised at highest rated voltage)
Operate for 96 hours at highest rated
voltage (HRV)
High temp. claim +70°C
(EUT not energised)
Storage for 96 hours
Hot start +65°C
(EUT energised at highest rated
voltage)
Operate for 2 hours at
highest rated voltage (HRV)
Last test +20°C (EUT energised) Functional verification tests for 2 hours
6.2 Cold test
IEC 60255-1,
IEC 60068-2-1: 2007
Start-up +20 °C (EUT energised) Functional verification tests for 2 hours
Intermediate 0°C (EUT energised) Functional verification tests for 2 hours
Intermediate -10°C (EUT energised)
Functional verification tests for 2 hours
Low temp. - 25°C (EUT energised)
Functional verification tests for 96 hours
Low temp. -25°C(EUT not energised) Storage for 96 hours
Cold start -25°C (EUT energised) Operate for 2 hours
Last test +20°C (EUT energised) Functional verification tests for 2 hours
6.3
Change of
temperature test
IEC 60255-1,
EN 60068-2-14:2009
Nb
Lower temperature -25°C
Higher temperature
+65°C
Rate of change of temperature
1°C/min
Duration of exposure 5 cycles
Duration of cycle 3 + 3 hrs.
EUT condition Energised
6.4
Damp heat steady
state test
EN 60068-2-78,
EN60068-2-30
Operating temperature +65°C
Humidity 93%
Duration of exposure 10 days
EUT condition Energised
6.5 Damp heat cyclic test
IEC60068-2-30
Lower temperature +25°C
Humidity 97%
Higher temperature
+65°C
Humidity
93%
Duration of exposure 6 cycles
Duration of cycle 12 + 12 hrs.
EUT condition Energised
6.6 Enclosure protection EN 60529:2000
IP52 For Front
IP20 For Rear
EUT condition Non energised