P50 Agile P253
5 Configuration
P253/EN M/C
5-51
Inh. Trip Dur St
Disabled
Editable setting
By using the (+ /5) or (- /6) key, Inh. Trip Dur St is set as Disabled.
K Coefficient
3
Editable setting
By using the (+ /5) or (- /6) key, the desired K Coefficient can be set.
The setting range is 0 to 10 step 1
Thermal Trip
Disabled
Editable setting
By using the (+ /5) or (- /6) key, Thermal Trip is set as Disabled.
Thermal Alarm
Disabled
Editable setting
By using the (+ /5) or (- /6) key, Thermal Alarm is set as Disabled.
Thermal Const. T1
20 Mins
Editable setting
By using the (+ /5) or (- /6) key, the desired Thermal Const.T1 can
be set. The setting range is from 1 to 180 Mins in steps of 1 Min.
Thermal Const. T2
20 Mins
Editable setting
By using the (+ /5) or (- /6) key, the desired Thermal Const.T2 can
be set. The setting range is from 1 to 360 Mins in steps of 1 Min.
Cooling Const.Tr
60 Mins
Editable setting
By using the (+ /5) or (- /6) key, the desired Thermal Const.Tr can be
set. The setting range is from 1 to 999 Mins in steps of 1 Min.
Thermal Lockout
Disabled
Editable setting
By using the (+ /5) or (- /6) key, Thermal Lockout is Disabled.
K
1
Editable setting
By using the (+ /5) or (- /6) key, the desired K value can be set. The
setting range is from 1 to 1.5 in steps of 0.01.