Chapter 2. LED Operation and Connector Details
GFK-2737F December 2016 23
2.1.8.6 Power-up LED Patterns
At power-up, the LEDs show the patterns described below. The LEDs also blink diagnostic patterns for
certain operating errors and for module identification. See the section on Special LED Blink Patterns above
for a description of the special blink patterns.
Figure 3: IC695PNS001 LEDs
OK LED blinks amber with
special blink code
Fatal initialization or diagnostics
Failure; Hardware Module Identity
Information not available.
STATUS LED blinks green
with special blink code
Fatal initialization failure.
OK, LAN, and STATUS LEDs
blink green in unison (1 Hz)
Invalid firmware detected or
firmware update initiated. Module is
waiting for firmware update. Blink
pattern continues during firmware
update. After the automatic update
completes, the LAN and STATUS
LEDs blink Amber and the module
resets, which restarts the power-up
process.
STATUS and LAN LEDs blink
green in unison (1 Hz)
Internal update in process following
a firmware update. Unit should
complete update and restart
automatically.
LAN and STATUS LED solid
green
Normal operation. Power-up
completed.
Note: Under certain ambient operating temperatures, the PROFINET Scanner may momentarily display
the over temperature pattern during power up, while it is calibrating its thermal protection
functions. This indication can be ignored. For details, refer to the section Microprocessor Over
Temperature above.