Chapter 3. Installation
GFK-2737F December 2016 31
3.3.4 Module Installation
RX3i rack power must be turned off. The
PNS does not support insertion/removal
while power is applied to the rack.
Figure 6: Install Module into RX3i Backplane
Holding the module firmly, align the module
with the correct slot and connector.
Engage the module’s rear pivot hook in the
notch on the top of the backplane (1).
Swing the module down (2) until the
module’s connector engages the
backplane’s backplane connector.
Visually inspect the module to be sure it is
properly seated.
Secure the bottom of the module to the
backplane using the machine screws
provided with the module (3).
Tighten the heat sink screw on the front of
the module in the threaded hole in the back
plate to 6 in-lbs (0.68 Nm), using a flat-tip
screwdriver.
3.3.5 Module Removal
RX3i rack power must be turned off.
Figure 7: Remove Module from RX3i Backplane
Loosen the heat sink screw on the front of
the module to release the heat sink from
the backplane’s aluminum back plate.
Loosen the screws at the bottom of the
module (1).
Pivot the module upward until its connector
is out of the backplane (2).
Lift the module up and away from the
backplane to disengage the pivot hook (3).