Chapter 6. Diagnostics
60 PACSystems* RX3i PROFINET IO-Scanner User Manual GFK-2737F
6.3 Fatal Error Handling
Any failures that occur during power-up or firmware update mode are considered fatal errors. This
includes faults detected on non-critical devices such as the USB port. After successful power-up of the
PROFINET Scanner, only catastrophic errors are treated as fatal. When a fatal error occurs, the PROFINET
scanner blinks an error code on its LEDs (refer to Section 2.1.8.1, Fatal Error Codes).
Certain conditions can prevent the module from powering up and becoming operational or entering
firmware update mode:
Problem
Indication
Action
Hardware failure
All LEDs off and the module is
unresponsive, or
The STATUS LED is solid Green
and is the only LED that is on.
Return the module to GE
Automation and Controls.
Invalid firmware
Power-up diagnostics/hardware
initializations failures that are considered
fatal
LED Fatal Error blink code
Note the blink code and
contact Customer Service
Catastrophic error during operation
LED Fatal Error blink code
Note the blink code and
contact Customer Service