EasyManua.ls Logo

GE SF6 - Page 30

GE SF6
300 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description and operation
Operating d evice of circuit- breaker
GE Information L14- 005EN/05
4/6
11- 2016
Operating principle
Warning
OPERATION AUTHORIZED ONLY IF THE OPERATING DEVICE IS CON-
NECTED TO THE CIRCUIT BREAKER.
THE CIRCUIT BREAKER MUST NOT BE OPERATED AT A SF
6
PRES-
SURE GAS LOWER THAN THE MINIMAL PRESSURE FOR THE INSULA-
TION p
me
.
Closing
D When the closing coil is energized or the manual closing lever is operated,
the closing latch (14) releases the inertia flywheel (8).
D The closing shaft (7) effects a 180 rotation generated by the loaded clos-
ing spring (9).
D The cam (10) rotates the main shaft (1) by means of the lever with roller
(11). After a 60 rotation, the lever (5) rests on the opening latch (6).
D Simultaneously, the opening spring (3) is loaded by means of the chain (34)
activated by the rotation of the lever (33).
D A freewheel, installed on the gear wheel (19), avoids the reducing gears
(13) and the motor (12) being driven by the gear wheel of the inertia flywheel
(8).
NOTE
: A mechanical device (not shown) prevents all closing opera-
tions if the circuit- breaker is already in the “CLOSED” position.
Diagram
27
11
10
34
22
13
8
9
12
19 14
6
3
1
28
7
5
24
33
Continued on next page.

Related product manuals