EasyManua.ls Logo

GE TRANSFIX DGA 500 - Table A-3: Access Flags; Table A-4: Modifier Flags

GE TRANSFIX DGA 500
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MA-014 - TRANSFIX DGA 500 User Guide Rev 1.1 13-Oct-15 Page 27 of 28
A.2.2 UNIX Time Example
For reference, the time on a device is reported in TransConnect as 12 Aug 2011 11:56:00
BST and the corresponding value in the registers mentioned above is 13146616.
When testing, please check that you are reading registers 1197-1198 (assuming
addresses start at 999 +1) and decoding an unsigned 32 bit big endian number. The
epoch time is in UTC. This matches the device time. An online converter e.g.
http://www.epochconverter.com/ can be used to verify.
A.2.3 Register Access Control
The product registers are protected with access flags. The register map details the
relevant access flags for each register. Each register may have one or more access flags,
separated by commas. Table A3 lists the supported access flags:
Table A3: Access flags
Access flags may be modified with the addition of the modifier flags listed in Table A4.
Table A4: Modifier flags
Flag
Access
Description
u
User
Only accessible if the master is authorised with user access
c
Config
Only accessible if master is authorised as config (commissioning) user
f
Factory
Only accessible if master is authorised as factory (service) user
Flag
Access
Description
r
Read
Read access to a single register
rgN
Read group
Read access to a group of length N (Nmax = 120)
w
Write
Write access to a single register
wgN
Write group
Write access to a group of length N (Nmax = 120)