GE Multilin L60 Line Phase Comparison System B-15
APPENDIX B B.4 MEMORY MAPPING
B
234C Fault 1 Prefault Phase B Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
234E Fault 1 Prefault Phase B Voltage Angle -359.9 to 0 degrees 0.1 F002 0
234F Fault 1 Prefault Phase C Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2351 Fault 1 Prefault Phase C Voltage Angle -359.9 to 0 degrees 0.1 F002 0
2352 Fault 1 Phase A Current Magnitude 0 to 999999.999 A 0.001 F060 0
2354 Fault 1 Phase A Current Angle -359.9 to 0 degrees 0.1 F002 0
2355 Fault 1 Phase B Current Magnitude 0 to 999999.999 A 0.001 F060 0
2357 Fault 1 Phase B Current Angle -359.9 to 0 degrees 0.1 F002 0
2358 Fault 1 Phase C Current Magnitude 0 to 999999.999 A 0.001 F060 0
235A Fault 1 Phase C Current Angle -359.9 to 0 degrees 0.1 F002 0
235B Fault 1 Phase A Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
235D Fault 1 Phase A Voltage Angle -359.9 to 0 degrees 0.1 F002 0
235E Fault 1 Phase B Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2360 Fault 1 Phase B Voltage Angle -359.9 to 0 degrees 0.1 F002 0
2361 Fault 1 Phase C Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2363 Fault 1 Phase C Voltage Angle -359.9 to 0 degrees 0.1 F002 0
2364 Fault 1 Type 0 to 11 --- 1 F148 0 (NA)
2365 Fault 1 Location based on Line length units (km or miles) -3276.7 to 3276.7 --- 0.1 F002 0
2366 ...Repeated for Fault 2
238C ...Repeated for Fault 3
23B2 ...Repeated for Fault 4
23D8 ...Repeated for Fault 5
Synchrocheck Actuals (Read Only) (2 modules)
2400 Synchrocheck 1 Delta Voltage -1000000000000 to
1000000000000
V 1 F060 0
2402 Synchrocheck 1 Delta Frequency 0 to 655.35 Hz 0.01 F001 0
2403 Synchrocheck 1 Delta Phase 0 to 179.9 degrees 0.1 F001 0
2404 ...Repeated for Synchrocheck 2
Autoreclose Status (Read Only) (6 modules)
2410 Autoreclose 1 Count 0 to 65535 --- 1 F001 0
2411 Autoreclose 2 Count 0 to 65535 --- 1 F001 0
2412 Autoreclose 3 Count 0 to 65535 --- 1 F001 0
2413 Autoreclose 4 Count 0 to 65535 --- 1 F001 0
2414 Autoreclose 5 Count 0 to 65535 --- 1 F001 0
2415 Autoreclose 6 Count 0 to 65535 --- 1 F001 0
Remote double-point status inputs (read/write setting registers and read only actaul value registers)
2608 Remote double-point status input 1 device 1 to 32 --- 1 F001 1
2609 Remote double-point status input 1 item 0 to 128 --- 1 F156 0 (None)
260A Remote double-point status input 1 name 1 to 64 --- 1 F205 "Rem Ip 1"
2610 Remote double-point status input 1 input state (read only) 0 to 3 --- 1 F605 3 (Bad)
2611 Remote double-point status input 1 events 0 to 1 --- 1 F102 0 (Disabled)
2612 ... Repeated for double-point status input 2 --- --- --- --- ---
261C ... Repeated for double-point status input 3 --- --- --- --- ---
2626 ... Repeated for double-point status input 4 --- --- --- --- ---
2630 ... Repeated for double-point status input 5 --- --- --- --- ---
Expanded FlexStates (Read Only)
2B00 FlexStates, one per register (256 items) 0 to 1 --- 1 F108 0 (Off)
Expanded Digital Input/Output states (Read Only)
2D00 Contact Input States, one per register (96 items) 0 to 1 --- 1 F108 0 (Off)
2D80 Contact Output States, one per register (64 items) 0 to 1 --- 1 F108 0 (Off)
2E00 Virtual Output States, one per register (96 items) 0 to 1 --- 1 F108 0 (Off)
Expanded Remote Input/Output Status (Read Only)
2F00 Remote Device States, one per register (16 items) 0 to 1 --- 1 F155 0 (Offline)
2F80 Remote Input States, one per register (64 items) 0 to 1 --- 1 F108 0 (Off)
Table B–9: MODBUS MEMORY MAP (Sheet 7 of 55)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT