GE Multilin L60 Line Phase Comparison System B-19
APPENDIX B B.4 MEMORY MAPPING
B
409C DNP Address 0 to 65519 --- 1 F001 1
409D Reserved 0 to 1 --- 1 F001 0
409E DNP Client Addresses (2 items) 0 to 4294967295 --- 1 F003 0
40A3 TCP Port Number for the Modbus protocol 1 to 65535 --- 1 F001 502
40A4 TCP/UDP Port Number for the DNP Protocol 1 to 65535 --- 1 F001 20000
40A5 TCP Port Number for the HTTP (Web Server) Protocol 1 to 65535 --- 1 F001 80
40A6 Main UDP Port Number for the TFTP Protocol 1 to 65535 --- 1 F001 69
40A7 Data Transfer UDP Port Numbers for the TFTP Protocol
(zero means “automatic”) (2 items)
0 to 65535 --- 1 F001 0
40A9 DNP Unsolicited Responses Function 0 to 1 --- 1 F102 0 (Disabled)
40AA DNP Unsolicited Responses Timeout 0 to 60 s 1 F001 5
40AB DNP unsolicited responses maximum retries 1 to 255 --- 1 F001 10
40AC DNP unsolicited responses destination address 0 to 65519 --- 1 F001 1
40AD Ethernet operation mode 0 to 1 --- 1 F192 0 (Half-Duplex)
40AE DNP current scale factor 0 to 8 --- 1 F194 2 (1)
40AF DNP voltage scale factor 0 to 8 --- 1 F194 2 (1)
40B0 DNP power scale factor 0 to 8 --- 1 F194 2 (1)
40B1 DNP energy scale factor 0 to 8 --- 1 F194 2 (1)
40B2 DNP power scale factor 0 to 8 --- 1 F194 2 (1)
40B3 DNP other scale factor 0 to 8 --- 1 F194 2 (1)
40B4 DNP current default deadband 0 to 65535 --- 1 F001 30000
40B6 DNP voltage default deadband 0 to 65535 --- 1 F001 30000
40B8 DNP power default deadband 0 to 65535 --- 1 F001 30000
40BA DNP energy default deadband 0 to 65535 --- 1 F001 30000
40BE DNP other default deadband 0 to 65535 --- 1 F001 30000
40C0 DNP IIN time synchronization bit period 1 to 10080 min 1 F001 1440
40C1 DNP message fragment size 30 to 2048 --- 1 F001 240
40C2 DNP client address 3 0 to 4294967295 --- 1 F003 0
40C4 DNP client address 4 0 to 4294967295 --- 1 F003 0
40C6 DNP client address 5 0 to 4294967295 --- 1 F003 0
40C8 DNP number of paired binary output control points 0 to 16 --- 1 F001 0
40C9 DNP TCP connection timeout 0 to 16 --- 1 F001 0
40CA Reserved (22 items) 0 to 1 --- 1 F001 0
40E0 TCP port number for the IEC 60870-5-104 protocol 1 to 65535 --- 1 F001 2404
40E1 IEC 60870-5-104 protocol function 0 to 1 --- 1 F102 0 (Disabled)
40E2 IEC 60870-5-104 protocol common address of ASDU 0 to 65535 --- 1 F001 0
40E3 IEC 60870-5-104 protocol cyclic data transmit period 1 to 65535 s 1 F001 60
40E4 IEC 60870-5-104 current default threshold 0 to 65535 --- 1 F001 30000
40E6 IEC 60870-5-104 voltage default threshold 0 to 65535 --- 1 F001 30000
40E8 IEC 60870-5-104 power default threshold 0 to 65535 --- 1 F001 30000
40EA IEC 60870-5-104 energy default threshold 0 to 65535 --- 1 F001 30000
40EC IEC 60870-5-104 power default threshold 0 to 65535 --- 1 F001 30000
40EE IEC 60870-5-104 other default threshold 0 to 65535 --- 1 F001 30000
40F0 IEC 60870-5-104 client address (5 items) 0 to 4294967295 --- 1 F003 0
40FD Reserved (60 items) 0 to 1 --- 1 F001 0
4140 DNP object 1 default variation 1 to 2 --- 1 F001 2
4141 DNP object 2 default variation 1 to 3 --- 1 F001 2
4142 DNP object 20 default variation 0 to 3 --- 1 F523 0 (1)
4143 DNP object 21 default variation 0 to 3 --- 1 F524 0 (1)
4144 DNP object 22 default variation 0 to 3 --- 1 F523 0 (1)
4145 DNP object 23 default variation 0 to 3 --- 1 F523 0 (1)
4146 DNP object 30 default variation 1 to 5 --- 1 F001 1
4147 DNP object 32 default variation 0 to 5 --- 1 F525 0 (1)
Table B–9: MODBUS MEMORY MAP (Sheet 11 of 55)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT