GE Multilin L60 Line Phase Comparison System B-35
APPENDIX B B.4 MEMORY MAPPING
B
70B0 ...Repeated for Phase Distance Zone 3
Ground Distance (Read/Write Grouped Setting) (5 modules)
7130 Ground Distance Zone 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7131 Ground Distance Zone 1 Current Supervision 0.05 to 30 pu 0.001 F001 200
7132 Ground Distance Zone 1 Reach 0.02 to 500 ohms 0.01 F001 200
7133 Ground Distance Zone 1 Direction 0 to 2 --- 1 F154 0 (Forward)
7134 Ground Distance Zone 1 Comparator Limit 30 to 90 degrees 1 F001 90
7135 Ground Distance Zone 1 Delay 0 to 65.535 s 0.001 F001 0
7136 Ground Distance Zone 1 Block 0 to 65535 --- 1 F300 0
7137 Ground Distance Zone 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7138 Ground Distance Zone 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7139 Ground Distance Zone 1 Shape 0 to 1 --- 1 F120 0 (Mho)
713A Ground Distance Zone 1 Z0 Z1 Magnitude 0 to 10 --- 0.01 F001 270
713B Ground Distance Zone 1 Z0 Z1 Angle -90 to 90 degrees 1 F002 0
713C Ground Distance Zone 1 RCA 30 to 90 degrees 1 F001 85
713D Ground Distance Zone 1 DIR RCA 30 to 90 degrees 1 F001 85
713E Ground Distance Zone 1 DIR Comp Limit 30 to 90 degrees 1 F001 90
713F Ground Distance Zone 1 Quad Right Blinder 0.02 to 500 ohms 0.01 F001 1000
7140 Ground Distance Zone 1 Quad Right Blinder RCA 60 to 90 degrees 1 F001 85
7141 Ground Distance Zone 1 Quad Left Blinder 0.02 to 500 ohms 0.01 F001 1000
7142 Ground Distance Zone 1 Quad Left Blinder RCA 60 to 90 degrees 1 F001 85
7143 Ground Distance Zone 1 Z0M Z1 Magnitude 0 to 7 --- 0.01 F001 0
7144 Ground Distance Zone 1 Z0M Z1 Angle -90 to 90 degrees 1 F002 0
7145 Ground Distance Zone 1 Voltage Level 0 to 5 pu 0.001 F001 0
7146 Ground Distance Zone 1 Non-Homogeneous Angle -40 to 40 degrees 0.1 F002 0
7147 Ground Distance Zone 1 POL Current 0 to 1 --- 1 F521 0 (Zero-seq)
7148 Ground Distance Zone 1 Reverse Reach 0.02 to 500 ohms 0.01 F001 200
7149 Ground Distance Zone 1 Reverse Reach RCA 30 to 90 degrees 1 F001 85
714A Reserved (7 items) 0 to 65535 --- 1 F001 0
7151 ...Repeated for Ground Distance Zone 2
7172 ...Repeated for Ground Distance Zone 3
Line Pickup (Read/Write Grouped Setting)
71F0 Line Pickup Function 0 to 1 --- 1 F102 0 (Disabled)
71F1 Line Pickup Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
71F2 Line Pickup Phase IOC Pickup 0 to 30 pu 0.001 F001 1000
71F3 Line Pickup UV Pickup 0 to 3 pu 0.001 F001 700
71F4 Line End Open Pickup Delay 0 to 65.535 s 0.001 F001 150
71F5 Line End Open Reset Delay 0 to 65.535 s 0.001 F001 90
71F6 Line Pickup OV Pickup Delay 0 to 65.535 s 0.001 F001 40
71F7 Autoreclose Coordination Pickup Delay 0 to 65.535 s 0.001 F001 45
71F8 Autoreclose Coordination Reset Delay 0 to 65.535 s 0.001 F001 5
71F9 Autoreclose Coordination Bypass 0 to 1 --- 1 F102 1 (Enabled)
71FA Line Pickup Block 0 to 65535 --- 1 F300 0
71FB Line Pickup Target 0 to 2 --- 1 F109 0 (Self-reset)
71FC Line Pickup Events 0 to 1 --- 1 F102 0 (Disabled)
71FD Terminal Open 0 to 65535 --- 1 F300 0
71FE Autoreclose Accelerate 0 to 65535 --- 1 F300 0
Phase Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7260 Phase Directional Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7261 Phase Directional Overcurrent 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
7262 Phase Directional Overcurrent 1 Block 0 to 65535 --- 1 F300 0
7263 Phase Directional Overcurrent 1 ECA 0 to 359 --- 1 F001 30
7264 Phase Directional Overcurrent 1 Pol V Threshold 0 to 3 pu 0.001 F001 700
7265 Phase Directional Overcurrent 1 Block Overcurrent 0 to 1 --- 1 F126 0 (No)
Table B–9: MODBUS MEMORY MAP (Sheet 27 of 55)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT