GE Multilin T60 Transformer Protection System 5-37
5 SETTINGS 5.2 PRODUCT SETUP
5
i) TFTP PROTOCOL
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS TFTP PROTOCOL
The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the T60 over a network. The T60 operates as a
TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file
obtained from the T60 contains a list and description of all available files (event records, oscillography, etc.).
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
j) IEC 60870-5-104 PROTOCOL
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 60870-5-104 PROTOCOL
The T60 supports the IEC 60870-5-104 protocol. The T60 can be used as an IEC 60870-5-104 slave device connected to a
maximum of two masters (usually either an RTU or a SCADA master station). Since the T60 maintains two sets of IEC
60870-5-104 data change buffers, no more than two masters should actively communicate with the T60 at one time.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
TFTP PROTOCOL
TFTP MAIN UDP PORT
NUMBER: 69
Range: 1 to 65535 in steps of 1
MESSAGE
TFTP DATA UDP PORT 1
NUMBER: 0
Range: 0 to 65535 in steps of 1
MESSAGE
TFTP DATA UDP PORT 2
NUMBER: 0
Range: 0 to 65535 in steps of 1
IEC 60870-5-104
PROTOCOL
IEC 60870-5-104
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
IEC TCP PORT
NUMBER: 2404
Range: 1 to 65535 in steps of 1
MESSAGE
IEC NETWORK
CLIENT ADDRESSES
MESSAGE
IEC COMMON ADDRESS
OF ASDU: 0
Range: 0 to 65535 in steps of 1
MESSAGE
IEC CYCLIC DATA
PERIOD: 60 s
Range: 1 to 65535 s in steps of 1
MESSAGE
IEC CURRENT DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC VOLTAGE DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC POWER DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC ENERGY DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC OTHER DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC REDUNDANCY
ENABLED: No
Range: No, Yes