GE Multilin T60 Transformer Protection System 2-15
2 PRODUCT DESCRIPTION 2.2 SPECIFICATIONS
2
2.2.3 MONITORING
OSCILLOGRAPHY
Maximum records: 64
Sampling rate: 64 samples per power cycle
Triggers: any element pickup, dropout, or operate;
digital input change of state; digital out-
put change of state; FlexLogic™ equa-
tion
Data: AC input channels; element state; digital
input state; digital output state
Data storage: in non-volatile memory
EVENT RECORDER
Capacity: 1024 events
Time-tag: to 1 microsecond
Triggers: any element pickup, dropout, or operate;
digital input change of state; digital out-
put change of state; self-test events
Data storage: in non-volatile memory
USER-PROGRAMMABLE FAULT REPORT
Number of elements: 2
Pre-fault trigger: any FlexLogic™ operand
Fault trigger: any FlexLogic™ operand
Recorder quantities: 32 (any FlexAnalog value)
DATA LOGGER
Number of channels: 1 to 16
Parameters: any available analog actual value
Sampling rate: 15 to 3600000 ms in steps of 1
Trigger: any FlexLogic™ operand
Mode: continuous or triggered
Storage capacity: (NN is dependent on memory)
1-second rate:
01 channel for NN days
16 channels for NN days
60-minute rate:
01 channel for NN days
16 channels for NN days
PHASOR MEASUREMENT UNIT
Output format: per IEEE C37.118 standard
Number of channels: 14 synchrophasors, 8 analogs, 16 digi-
tals
TVE (total vector error) <1%
Triggering: frequency, voltage, current, power, rate
of change of frequency, user-defined
Reporting rate: 1, 2, 5, 10, 12, 15, 20, 25, 30, 50, or 60
times per second
Number of clients: One over TCP/IP port, two over UDP/IP
ports
AC ranges: As indicated in appropriate specifications
sections
Network reporting format: 16-bit integer or 32-bit IEEE floating
point numbers
Network reporting style: rectangular (real and imaginary) or polar
(magnitude and angle) coordinates
Post-filtering: none, 3-point, 5-point, 7-point
Calibration: ±5°
2.2.4 METERING
RMS CURRENT: PHASE, NEUTRAL, AND GROUND
Accuracy at
0.1 to 2.0 × CT rating: ±0.25% of reading or ±0.1% of rated
(whichever is greater)
> 2.0 × CT rating: ±1.0% of reading
RMS VOLTAGE
Accuracy: ±0.5% of reading from 10 to 208 V
REAL POWER (WATTS)
Accuracy: ±1.0% of reading at
–0.8 < PF –1.0 and 0.8 < PF 1.0
REACTIVE POWER (VARS)
Accuracy: ±1.0% of reading at –0.2 PF 0.2
APPARENT POWER (VA)
Accuracy: ±1.0% of reading
WATT-HOURS (POSITIVE AND NEGATIVE)
Accuracy: ±2.0% of reading
Range: ±0 to 1 × 10
6
MWh
Parameters: three-phase only
Update rate: 50 ms
VAR-HOURS (POSITIVE AND NEGATIVE)
Accuracy: ±2.0% of reading
Range: ±0 to 1 × 10
6
Mvarh
Parameters: three-phase only
Update rate: 50 ms