EasyManua.ls Logo

GE UR T60 - Test Example 3

GE UR T60
724 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9-10 T60 Transformer Protection System GE Multilin
9.2 DIFFERENTIAL CHARACTERISTIC TEST EXAMPLES 9 COMMISSIONING
9
9.2.4 TEST EXAMPLE 3
Yg/D30° TRANSFORMER WITH PHASE B TO C FAULT ON THE DELTA SIDE.
Transformer: Y/D30°, 20 MVA, 115/12.47 kv, CT1 (200:1), CT2 (1000:1)
Figure 9–4: CURRENT DISTRIBUTION ON A YG/D30° TRANSFORMER WITH AN a TO b FAULT ON THE LV SIDE
Three adjustable currents are required in this case. The Phase A and C Wye-side line currents, identical in magnitude but
displaced by 180°, can be simulated with one current source passed through these relay terminals in series. The second
current source simulates the Phase B primary current. The third source simulates the delta “b” and “c” phase currents, also
equal in magnitude but displaced by 180°.
TEST PHASE INJECTED CURRENT DISPLAYED CURRENT STATUS
W1 CURRENT W2 CURRENT DIFFERENTIAL RESTRAINT
Balanced
Condition
A 0.25 0 0 0 Not Applicable
B0.5 –180° 0.8 0 0.8
C 0.25 0.8 –180° 0 0.8 –180°
Min Pickup
change the
Min PKP to
0.2 pu
A 0.25 0 0 0 Block
I
d
= 0.051 < Min PKP
B0.5 –180° 0.95 0.154 0.948
C 0.25 0.95 –180° 0.155 0.950 –180°
Minimum
Pickup
A 0.25 0 0 0 Operate
I
d
= 0.102 > Min PKP
B0.5 –180° 1.05 0.253 1.049
C 0.25 1.05 –180° 0.255 1.050 –180°
Slope 1
return the
Min PKP to
0.1 pu
A 0.25 0 0 0 Block
I
d
/I
r
= 13.2%
B0.5 –180° 0.92 0.123 0.919
C 0.25 0.92 –180° 0.123 0.919 –180°
Slope 1 A 0.25 0 0 0 Operate
I
d
/I
r
= 15.9%
B0.5 –180° 0.95 0.153 0.948
C 0.25 0.95 –180° 0.153 0.948 –180°
Intermediate
Slope 1 & 2
A2 0 0 0 Block
I
d
/I
r
= 84.3%
< 86.6%
computed
B4 –180° 1 5.37 –180° 6.37
C2 1 –180° 5.37 6.37 –180°
Intermediate
Slope 1 & 2
A2 0 0 0 Operate
I
d
/I
r
= 87.5%
> 86.6%
computed
B4 –180° 0.8 5.57 –180° 6.37
C2 0.8 –180° 5.57 6.37 –180°
Slope 2 A 4 0 0 0 Block
I
d
/I
r
= 93.7%
< Slope 2 = 95%
B8 –180° 0.8 11.93 –180° 12.73
C4 0.8 –180° 11.93 12.73 –180°
Slope 2 A 4 0 0 0 Operate
I
d
/I
r
= 95.7%
> Slope 2 = 95%
B8 –180° 0.6 12.13 –180° 12.73
C4 0.6 –180° 12.13 12.73 –180°
828738A1.CDR
Y/d30° Transformer
F
I (f) = 0.5 pu –270°
A
I (f) = 0.866 pu –90°
b
I(f)=0
a
I (f) = 0.866 pu –270°
c
I (f) = 1 pu –90°
B
I (f) = 0.5 pu –270°
C
A
B
C
A
B
C

Table of Contents

Related product manuals