5-108 T60 Transformer Protection System GE Multilin
5.4 SYSTEM SETUP 5 SETTINGS
5
d) PMU COMMUNICATION
PATH: SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT...  PMU 1 COMMUNICATION  PMU 1 COMM PORT
This section configures the phasor measurement unit (PMU) communication functions.
PMU1 COMM PORT: This setting specifies the communication port for transmission of the PMU data.
PMU 1
COMM PORT 1
PMU1 COMM PORT:
None
Range: None, Network, GOOSE
MESSAGE
PMU1 PORT PHS-1
PMU 1 V1
Range: available synchrophasor values
MESSAGE
PMU1 PORT PHS-1
NM: GE-UR-PMU1-V1
Range: 16-character ASCII string
MESSAGE
PMU1 PORT PHS-14
PMU 1 V1
Range: available synchrophasor values
MESSAGE
PMU1 PORT PHS-14
NM: GE-UR-PMU1-V1
Range: 16 alphanumeric characters
MESSAGE
PMU1 PORT A-CH-1:
Off
Range: available FlexAnalog values
MESSAGE
PMU1 PORT A-CH-1
NM: AnalogChannel1
Range: 16 alphanumeric characters
MESSAGE
PMU1 PORT A-CH-8:
Off
Range: available FlexAnalog values
MESSAGE
PMU1 PORT A-CH-8
NM: AnalogChannel8
Range: 16 alphanumeric characters
MESSAGE
PMU1 PORT D-CH-1:
Off
Range: FlexLogic™ operands
MESSAGE
PMU1 PORT D-CH-1
NM: DigitalChannel1
Range: 16 alphanumeric characters
MESSAGE
PMU1 PORT D-CH-1
NORMAL STATE: Off
Range: On, Off
MESSAGE
PMU1 PORT D-CH-16:
Off
Range: FlexLogic™ operands
MESSAGE
PMU1 PORT D-CH-16
NM: DigitalChannel16
Range: 16 alphanumeric characters
MESSAGE
PMU1 PORT D-CH-16
NORMAL STATE: Off
Range: On, Off