5-178 T60 Transformer Protection System GE Multilin
5.6 GROUPED ELEMENTS 5 SETTINGS
5
c) INSTANTANEOUS DIFFERENTIAL
PATH: SETTINGS  GROUPED ELEMENTS SETTING GROUP 1(6) TRANSFORMER  INSTANTANEOUS DIFFERENTIAL
The instantaneous differential element acts as an instantaneous overcurrent element responding to the measured differen-
tial current magnitude (filtered fundamental frequency component) and applying a user-selectable pickup threshold. The
pickup threshold should be set greater than the maximum spurious differential current that could be encountered under
non-internal fault conditions (typically magnetizing inrush current or an external fault with extremely severe CT saturation).
Figure 5–91: INSTANTANEOUS DIFFERENTIAL SCHEME LOGIC
d) HOTTEST-SPOT TEMPERATURE
PATH: SETTINGS  GROUPED ELEMENTS SETTING GROUP 1(6) TRANSFORMER  HOTTEST-SPOT TEMPERATURE
The Hottest-Spot Temperature element provides a mechanism for detecting abnormal winding hottest-spot temperatures
inside the transformer. It can be set to alarm or trip in cases where the computed hottest-spot temperature is above the
pickup threshold for a user-specified time (considered as transformer overheating).
INSTANTANEOUS
DIFFERENTIAL
INST DIFFERENTIAL
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
INST DIFFERENTIAL
PICKUP: 8.000 pu
Range: 2.000 to 30.000 pu in steps of 0.001
MESSAGE
INST DIFF BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
INST DIFFERENTIAL
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
INST DIFFERENTIAL
EVENTS: Disabled
Range: Disabled, Enabled
HOTTEST-SPOT
TEMPERATURE
XFMR HST FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
XFMR HST PICKUP:
140°C
Range: 50 to 300°C in steps of 1
MESSAGE
XFMR HST DELAY:
1 min.
Range: 0 to 30000 min. in steps of 1
MESSAGE
XFMR HST BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
XFMR HST TARGET:
Self-Reset
Range: Self-reset, Latched, Disabled
SETTING
ACTUAL VALUE
SETTING
SETTING
FLEXLOGIC OPERAND
FLEXLOGIC OPERANDS
INST DIFFERENTIAL
FUNCTION:
DIFF PHASOR
INST DIFF BLOCK:
INST DIFFERENTIAL
PICKUP:
XFMR INST DIFF OP
XFMR INST DIFF OP C
XFMR INST DIFF OP B
XFMR INST DIFF OP A
Off=0
Enabled=1
Disabled=0
AND
828000A1.CDR
RUN
RUN
RUN
Iad > PICKUP
Iad
Ibd
Icd
Ibd > PICKUP
Icd > PICKUP
OR