B-24 T60 Transformer Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
Field Unit RTDs (Read/Write Setting) (8 modules)
3E80 Field Unit RTD 1Name 0 to 1 --- 1 F205 "RTD 1"
3E86 Field Unit RTD 1 Origin 0 to 24 --- 1 F253 0 (None)
3E87 Field Unit RTD 1 Type 0 to 2 --- 1 F259 0 (100 Ohm Nickel)
3E88 ...Repeated for Field Unit RTD 2
3E90 ...Repeated for Field Unit RTD 3
3E98 ...Repeated for Field Unit RTD 4
3EA0 ...Repeated for Field Unit RTD 5
3EA8 ...Repeated for Field Unit RTD 6
3EB0 ...Repeated for Field Unit RTD 7
3EB8 ...Repeated for Field Unit RTD 8
Field Unit Transducers (Read/Write Setting) (8 modules)
3ED0 Field Unit Transducer 1 Name 0 to 1 --- 1 F205 "TRD 1"
3ED6 Field Unit Transducer 1 Origin 0 to 24 --- 1 F253 0 (None)
3ED7 Field Unit Transducer 1 Range 0 to 9 --- 1 F246 6 (0...20mA)
3ED8 Field Unit Transducer 1 Min Value -9999.999 to 9999.999 --- 0.001 F004 0
3EDA Field Unit Transducer 1 Max Value -9999.999 to 9999.999 --- 0.001 F004 100000
3EDC Field Unit Transducer 1 Units --- --- --- F206 (none)
3EDF ...Repeated for Field Unit Transducer 2
3EEE ...Repeated for Field Unit Transducer 3
3EFD ...Repeated for Field Unit Transducer 4
3F0C ...Repeated for Field Unit Transducer 5
3F1B ...Repeated for Field Unit Transducer 6
3F2A ...Repeated for Field Unit Transducer 7
3F39 ...Repeated for Field Unit Transducer 8
Field Unit Identifiers (Read Only) (8 modules)
3F80 Attached Field Unit 1 Serial Number --- --- 1 F205 (none)
3F86 Attached Filed Unit 1 Port Number --- --- 1 F001 0
3F87 Attached Field Unit 1 Type 0 to 3 --- 1 F243 0 (CC-05)
3F88 Field Unit 1 Status 0 to 4 --- 1 F262 0 (Disabled)
3F89 ...Repeated for Field Unit 2
3F92 ...Repeated for Field Unit 3
3F9B ...Repeated for Field Unit 4
3FA4 ...Repeated for Field Unit 5
3FAD ...Repeated for Field Unit 6
3FB6 ...Repeated for Field Unit 7
3FBF ...Repeated for Field Unit 8
Passwords (Read/Write Command)
4000 Command Password Setting 0 to 4294967295 --- 1 F003 0
Passwords (Read/Write Setting)
4002 Setting Password Setting 0 to 4294967295 --- 1 F003 0
Passwords (Read/Write)
4008 Command Password Entry 0 to 4294967295 --- 1 F003 0
400A Setting Password Entry 0 to 4294967295 --- 1 F003 0
Passwords (Read Only Actual Values)
4010 Command Password Status 0 to 1 --- 1 F102 0 (Disabled)
4011 Setting Password Status 0 to 1 --- 1 F102 0 (Disabled)
Passwords (Read/Write Settings)
4012 Command Password Access Timeout 5 to 480 minutes 1 F001 5
4013 Setting Password Access Timeout 5 to 480 minutes 1 F001 30
4014 Invalid Password Attempts (before lockout) 2 to 5 --- 1 F001 3
4015 Password Lockout Duration 5 to 60 minutes 1 F001 5
4016 Password Access Events 0 to 1 --- 1 F102 0 (Disabled)
4017 Local Setting Authorization 1 to 65535 --- 1 F300 1
Table B–10: MODBUS MEMORY MAP (Sheet 16 of 65)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT