GE Multilin T60 Transformer Protection System B-45
APPENDIX B B.4 MEMORY MAPPING
B
Underfrequency (Read/Write Setting) (6 modules)
7E10 Underfrequency Function 0 to 1 --- 1 F102 0 (Disabled)
7E11 Underfrequency 1 Block 0 to 65535 --- 1 F300 0
7E12 Underfrequency 1 Minimum Current 0.1 to 1.25 pu 0.01 F001 10
7E13 Underfrequency 1 Pickup 20 to 65 Hz 0.01 F001 5950
7E14 Underfrequency 1 Pickup Delay 0 to 65.535 s 0.001 F001 2000
7E15 Underfrequency 1 Reset Delay 0 to 65.535 s 0.001 F001 2000
7E16 Underfrequency 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
7E17 Underfrequency 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7E18 Underfrequency 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7E19 Underfrequency 1 Reserved (8 items) 0 to 1 --- 1 F001 0
7E21 ...Repeated for Underfrequency 2
7E32 ...Repeated for Underfrequency 3
7E43 ...Repeated for Underfrequency 4
7E54 ...Repeated for Underfrequency 5
7E65 ...Repeated for Underfrequency 6
Neutral Overvoltage (Read/Write Grouped Setting) (3 modules)
7F00 Neutral Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7F01 Neutral Overvoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7F02 Neutral Overvoltage 1 Pickup 0 to 3 pu 0.001 F001 300
7F03 Neutral Overvoltage 1 Pickup Delay 0 to 600 s 0.01 F001 100
7F04 Neutral Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100
7F05 Neutral Overvoltage 1 Block 0 to 65535 --- 1 F300 0
7F06 Neutral Overvoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7F07 Neutral Overvoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7F08 Neutral Overvoltage 1 Curves 0 to 3 --- 1 F116 0 (Definite Time)
7F09 Reserved (7 items) 0 to 65535 --- 1 F001 0
7F10 ...Repeated for Neutral Overvoltage 2
7F20 ...Repeated for Neutral Overvoltage 3
Auxiliary Overvoltage (Read/Write Grouped Setting) (3 modules)
7F30 Auxiliary Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7F31 Auxiliary Overvoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7F32 Auxiliary Overvoltage 1 Pickup 0 to 3 pu 0.001 F001 300
7F33 Auxiliary Overvoltage 1 Pickup Delay 0 to 600 s 0.01 F001 100
7F34 Auxiliary Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100
7F35 Auxiliary Overvoltage 1 Block 0 to 65535 --- 1 F300 0
7F36 Auxiliary Overvoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7F37 Auxiliary Overvoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7F38 Reserved (8 items) 0 to 65535 --- 1 F001 0
7F40 ...Repeated for Auxiliary Overvoltage 2
7F50 ...Repeated for Auxiliary Overvoltage 3
Auxiliary Undervoltage (Read/Write Grouped Setting) (3 modules)
7F60 Auxiliary Undervoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7F61 Auxiliary Undervoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7F62 Auxiliary Undervoltage 1 Pickup 0 to 3 pu 0.001 F001 700
7F63 Auxiliary Undervoltage 1 Delay 0 to 600 s 0.01 F001 100
7F64 Auxiliary Undervoltage 1 Curve 0 to 1 --- 1 F111 0 (Definite Time)
7F65 Auxiliary Undervoltage 1 Minimum Voltage 0 to 3 pu 0.001 F001 100
7F66 Auxiliary Undervoltage 1 Block 0 to 65535 --- 1 F300 0
7F67 Auxiliary Undervoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7F68 Auxiliary Undervoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7F69 Reserved (7 items) 0 to 65535 --- 1 F001 0
7F70 ...Repeated for Auxiliary Undervoltage 2
7F80 ...Repeated for Auxiliary Undervoltage 3
Table B–10: MODBUS MEMORY MAP (Sheet 37 of 65)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT

Table of Contents