GE Multilin T60 Transformer Protection System B-47
APPENDIX B B.4 MEMORY MAPPING
B
8612 Breaker Failure 1 Phase Amp Hiset Pickup 0.001 to 30 pu 0.001 F001 1050
8613 Breaker Failure 1 Neutral Amp Hiset Pickup 0.001 to 30 pu 0.001 F001 1050
8614 Breaker Failure 1 Phase Amp Loset Pickup 0.001 to 30 pu 0.001 F001 1050
8615 Breaker Failure 1 Neutral Amp Loset Pickup 0.001 to 30 pu 0.001 F001 1050
8616 Breaker Failure 1 Loset Time 0 to 65.535 s 0.001 F001 0
8617 Breaker Failure 1 Trip Dropout Delay 0 to 65.535 s 0.001 F001 0
8618 Breaker Failure 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
8619 Breaker Failure 1 Events 0 to 1 --- 1 F102 0 (Disabled)
861A Breaker Failure 1 Phase A Initiate 0 to 65535 --- 1 F300 0
861B Breaker Failure 1 Phase B Initiate 0 to 65535 --- 1 F300 0
861C Breaker Failure 1 Phase C Initiate 0 to 65535 --- 1 F300 0
861D Breaker Failure 1 Breaker Status 1 Phase B 0 to 65535 --- 1 F300 0
861E Breaker Failure 1 Breaker Status 1 Phase C 0 to 65535 --- 1 F300 0
861F Breaker Failure 1 Breaker Status 2 Phase B 0 to 65535 --- 1 F300 0
8620 Breaker Failure 1 Breaker Status 2 Phase C 0 to 65535 --- 1 F300 0
8621 ...Repeated for Breaker Failure 2
8642 ...Repeated for Breaker Failure 3
8663 ...Repeated for Breaker Failure 4
8684 ...Repeated for Breaker Failure 5
86A5 ...Repeated for Breaker Failure 6
Remote RTD Inputs (Read/Write Grouped Setting) (12 modules)
86D0 Remote RTD 1 Function 0 to 1 --- 1 F102 0 (Disabled)
86D1 Remote RTD 1 ID --- --- --- F205 "RRTD 1"
86D7 Remote RTD 1 Type 0 to 3 --- 1 F174 0 (100 Ohm Platinum)
86D8 Remote RTD 1 Application 0 to 5 --- 1 F550 0 (None)
86D9 Remote RTD 1 Alarm Temperature 1 to 200 °C 1 F001 130
86DA Remote RTD 1 Alarm Pickup Delay 5 to 600 seconds 5 F001 5
86DB Remote RTD 1 Trip Temperature 1 to 200 °C 1 F001 130
86DC Remote RTD 1 Trip Pickup Delay 5 to 600 seconds 5 F001 5
86DD Remote RTD 1 Trip Reset Delay 5 to 600 seconds 5 F001 5
86DE Remote RTD 1 Trip Voting 0 to 13 --- 1 F603 0 (None)
86DF Remote RTD 1 Block 0 to 65535 --- 1 F300 0
86E0 Remote RTD 1 Open 0 to 2 --- 1 F552 0 (None)
86E1 Remote RTD 1 Target 0 to 2 --- 1 F109 0 (Self-Reset)
86E2 Remote RTD 1 Events 0 to 1 --- 1 F102 0 (Disabled)
86E3 Repeated for Remote RTD Input 2
86F6 Repeated for Remote RTD Input 3
8709 Repeated for Remote RTD Input 4
871C Repeated for Remote RTD Input 5
872F Repeated for Remote RTD Input 6
8742 Repeated for Remote RTD Input 7
8755 Repeated for Remote RTD Input 8
8768 Repeated for Remote RTD Input 9
877B Repeated for Remote RTD Input 10
878E Repeated for Remote RTD Input 11
87A1 Repeated for Remote RTD Input 12
Remote RTD Inputs (Read Only Actual Values) (12 modules)
87C0 Remote RTD 1 Value 0 to 200 °C 1 F002 0
87C1 Remote RTD 2 Value 0 to 200 °C 1 F002 0
87C2 Remote RTD 3 Value 0 to 200 °C 1 F002 0
87C3 Remote RTD 4 Value 0 to 200 °C 1 F002 0
87C4 Remote RTD 5 Value 0 to 200 °C 1 F002 0
87C5 Remote RTD 6 Value 0 to 200 °C 1 F002 0
87C6 Remote RTD 7 Value 0 to 200 °C 1 F002 0
Table B–10: MODBUS MEMORY MAP (Sheet 39 of 65)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT