GE Multilin T60 Transformer Protection System B-49
APPENDIX B B.4 MEMORY MAPPING
B
8CE4 ...Repeated for Digital Element 38
8CF8 ...Repeated for Digital Element 39
8D0C ...Repeated for Digital Element 40
8D20 ...Repeated for Digital Element 41
8D34 ...Repeated for Digital Element 42
8D48 ...Repeated for Digital Element 43
8D5C ...Repeated for Digital Element 44
8D70 ...Repeated for Digital Element 45
8D84 ...Repeated for Digital Element 46
8D98 ...Repeated for Digital Element 47
8DAC ...Repeated for Digital Element 48
Trip Bus (Read/Write Setting) (6 modules)
8E00 Trip Bus 1 Function 0 to 1 --- 1 F102 0 (Disabled)
8E01 Trip Bus 1 Block 0 to 65535 --- 1 F300 0
8E02 Trip Bus 1 Pickup Delay 0 to 600 s 0.01 F001 0
8E03 Trip Bus 1 Reset Delay 0 to 600 s 0.01 F001 0
8E04 Trip Bus 1 Input 1 0 to 65535 --- 1 F300 0
8E05 Trip Bus 1 Input 2 0 to 65535 --- 1 F300 0
8E06 Trip Bus 1 Input 3 0 to 65535 --- 1 F300 0
8E07 Trip Bus 1 Input 4 0 to 65535 --- 1 F300 0
8E08 Trip Bus 1 Input 5 0 to 65535 --- 1 F300 0
8E09 Trip Bus 1 Input 6 0 to 65535 --- 1 F300 0
8E0A Trip Bus 1 Input 7 0 to 65535 --- 1 F300 0
8E0B Trip Bus 1 Input 8 0 to 65535 --- 1 F300 0
8E0C Trip Bus 1 Input 9 0 to 65535 --- 1 F300 0
8E0D Trip Bus 1 Input 10 0 to 65535 --- 1 F300 0
8E0E Trip Bus 1 Input 11 0 to 65535 --- 1 F300 0
8E0F Trip Bus 1 Input 12 0 to 65535 --- 1 F300 0
8E10 Trip Bus 1 Input 13 0 to 65535 --- 1 F300 0
8E11 Trip Bus 1 Input 14 0 to 65535 --- 1 F300 0
8E12 Trip Bus 1 Input 15 0 to 65535 --- 1 F300 0
8E13 Trip Bus 1 Input 16 0 to 65535 --- 1 F300 0
8E14 Trip Bus 1 Latching 0 to 1 --- 1 F102 0 (Disabled)
8E15 Trip Bus 1 Reset 0 to 65535 --- 1 F300 0
8E16 Trip Bus 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
8E16 Trip Bus 1 Events 0 to 1 --- 1 F102 0 (Disabled)
8E18 Reserved (8 items) 0 to 1 --- 1 F001 0
8E20 ...Repeated for Trip Bus 2
8E40 ...Repeated for Trip Bus 3
8E60 ...Repeated for Trip Bus 4
8E80 ...Repeated for Trip Bus 5
8EA0 ...Repeated for Trip Bus 6
FlexElement (Read/Write Setting) (16 modules)
9000 FlexElement™ 1 Function 0 to 1 --- 1 F102 0 (Disabled)
9001 FlexElement™ 1 Name --- --- --- F206 “FxE 1”
9004 FlexElement™ 1 InputP 0 to 65535 --- 1 F600 0
9005 FlexElement™ 1 InputM 0 to 65535 --- 1 F600 0
9006 FlexElement™ 1 Compare 0 to 1 --- 1 F516 0 (LEVEL)
9007 FlexElement™ 1 Input 0 to 1 --- 1 F515 0 (SIGNED)
9008 FlexElement™ 1 Direction 0 to 1 --- 1 F517 0 (OVER)
9009 FlexElement™ 1 Hysteresis 0.1 to 50 % 0.1 F001 30
900A FlexElement™ 1 Pickup -90 to 90 pu 0.001 F004 1000
900C FlexElement™ 1 DeltaT Units 0 to 2 --- 1 F518 0 (Milliseconds)
900D FlexElement™ 1 DeltaT 20 to 86400 --- 1 F003 20
Table B–10: MODBUS MEMORY MAP (Sheet 41 of 65)