GE Multilin T60 Transformer Protection System B-73
APPENDIX B B.4 MEMORY MAPPING
B
D49D PMU 1 Port 2 PHS-x Name (14 items) --- --- --- F203 “GE-UR-PMU-PHS 1”
D50D PMU 1 Port 3 PHS-x Name (14 items) --- --- --- F203 “GE-UR-PMU-PHS 1”
D57D PMU 1 Port 1 A-CH-x (8 items) 0 to 65535 --- 1 F600 0
D585 PMU 1 Port 2 A-CH-x (8 items) 0 to 65535 --- 1 F600 0
D58D PMU 1 Port 3 A-CH-x (8 items) 0 to 65535 --- 1 F600 0
D595 PMU 1 Port 1 A-CH-x Name (8 items) --- --- --- F203 “AnalogChannel 1”
D5D5 PMU 1 Port 2 A-CH-x Name (8 items) --- --- --- F203 “AnalogChannel 1”
D615 PMU 1 Port 3 A-CH-x Name (8 items) --- --- --- F203 “AnalogChannel 1”
D655 PMU 1 Port 1 D-CH-x (16 items) 0 to 65535 --- 1 F300 0
D665 PMU 1 Port 2 D-CH-x (16 items) 0 to 65535 --- 1 F300 0
D675 PMU 1 Port 3 D-CH-x (16 items) 0 to 65535 --- 1 F300 0
D685 PMU 1 Port 1 D-CH-x Name (16 items) --- --- --- F203 “Dig Channel 1”
D705 PMU 1 Port 2 D-CH-x Name (16 items) --- --- --- F203 “Dig Channel 1”
D785 PMU 1 Port 3 D-CH-x Name (16 items) --- --- --- F203 “Dig Channel 1”
D805 PMU 1 Port 1 D-CH-x Normal State (16 items) 0 to 1 --- 1 F108 0 (Off)
D815 PMU 1 Port 2 D-CH-x Normal State (16 items) 0 to 1 --- 1 F108 0 (Off)
D825 PMU 1 Port 3 D-CH-x Normal State (16 items) 0 to 1 --- 1 F108 0 (Off)
Phasor Measurement Unit Recording Command (Read/Write Command)
E4D4 PMU 1 Recording Clear Command 0 to 1 --- 1 F126 0 (No)
E4D5 PMU 1 Recording Force Trigger 0 to 1 --- 1 F126 0 (No)
Phasor Measurement Unit Recording (Read/Write Setting)
E4DC PMU 1 Recording Rate 0 to 10 --- 1 F544 3 (5/sec.)
E4DD PMU 1 No of Timed Records 2 to 128 --- 1 F001 10
E4DE PMU 1 Trigger Mode 0 to 1 --- 1 F542 0 (Auto Overwrite)
E4DF PMU 1 Timed Trigger Position 1 to 50 % 1 F001 10
E4E0 PMU 1 Record PHS-1 (14 items) 0 to 14 --- 1 F543 1 (Va)
E4EE PMU 1 Record PHS-x Name (14 items) --- --- --- F203 "GE-UR-PMU-PHS
1"
E55E PMU 1 Record A-CH-x (8 items) 0 to 65535 --- 1 F600 0
E566 PMU 1 Record A-CH-x Name (8 items) --- --- --- F203 "AnalogChannel 1"
E5A6 PMU 1 Record D-CH-x (16 items) 0 to 65535 --- 1 F300 0
E5B6 PMU 1 Record D-CH-x Name (16 items) --- --- --- F203 "Dig Channel 1"
Phasor Measurement Unit Frequency Trigger (Read/Write Setting)
ECCC PMU 1 Frequency Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
ECCD PMU 1 Frequency Trigger Low Frequency 20 to 70 Hz 0.01 F001 4900
ECCE PMU 1 Frequency Trigger High Frequency 20 to 70 Hz 0.01 F001 6100
ECCF PMU 1 Frequency Trigger Pickup Time 0 to 600 s 0.01 F001 10
ECD0 PMU 1 Frequency Trigger Dropout Time 0 to 600 s 0.01 F001 100
ECD1 PMU 1 Frequency Trigger Block (3 items) 0 to 65535 --- 1 F300 0
ECD4 PMU 1 Frequency Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
ECD5 PMU 1 Frequency Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
Settings File Template (Read/Write Setting)
ED00 FlexLogic™ Displays Active 0 to 1 --- 1 F102 1 (Enabled)
ED01 Reserved (6 items) --- --- --- F205 (none)
Setting File Template (Read Only Non-Volatile)
ED07 Last Settings Change Date 0 to 4294967295 --- 1 F050 0
Settings File Template (Read/Write Setting)
ED09 Template Bitmask (750 items) 0 to 65535 --- 1 F001 0
Phasor Measurement Unit Records (Read Only)
EFFF PMU Recording Number of Triggers 0 to 65535 --- 1 F001 0
Table B–10: MODBUS MEMORY MAP (Sheet 65 of 65)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT