GFK-1504N Chapter 2 Installation 2-23
2
Wiring for a Barrier-Style I/O Carrier (IC200CHS001)
Field Wiring
Terminals
H
G
F
8
2
4
6
B
C
7
D
3
Each terminal on a Barrier-Style I/O Carrier accommodates one or two solid or
stranded wires from AWG #22 (avg. 0.36mm
2
cross section) to AWG #14
(avg. 2.1mm
2
cross section). Use copper wire rated for 90 degrees C. When
inserting two wires in the same position, the wires must be the same size and
type (solid or stranded).
The I/O carrier can accommodate current levels up to 2 Amps per point or 8
Amps per each power and ground, and a voltage range of up to 264 V AC.
Voltage transients up to 300 V AC will not damage the carrier.
For a Barrier-Style I/O Carrier, recommended terminal torque is 0.37 to 0.50 ft-lbs.
The label provided with the module can be folded and inserted in the module’s
transparent door.
Terminal Numbering for a Barrier-Style I/O Carrier