EasyManuals Logo

GE WavePro LVPCB User Manual

GE WavePro LVPCB
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
Ground-Fault Protection (Optional)
Ground-Fault Protection
A ground fault is an unintentional current flow from a
circuit through a conductive path to ground. Ground
faults usually have intermit-
tent or very low values of
current flow as depicted in
Graph A , and are not
detected by long-time over-
load protection. Some
ground-fault trip systems
may not detect this type of
fault because the intermit-
tent nature of the fault
never exceeds the trip
threshold as illustrated in Graph B . The MicroVersaTrip
Plus™ and MicroVersaTrip PM™ trip units detect and
integrate (add a series of arcing and intermittent current
pulses) the low-level current of a ground fault. This integra-
tion function provides a memory response for ground faults
to achieve preferred ground fault protection as shown in
Graph C . The NEC requires that the maximum ground-
fault setting not exceed 1200 amps. Ground-fault protection
includes independent pickup and delay settings and
selectable I
2
t function.
Ground-fault pickup settings are based on multiples of CT,
the current sensor rating. The lowest setting is 20% of CT,
and the highest setting is based on current sensor amp rat-
ings, such that the maximum setting does not exceed 1200
amps. There are three ground-fault delay bands of 1 (MIN),
2 (INT), 3 (MAX) ranging from 100 ms to 350 ms. The I
2
t
function modifies the square corner of the ground-fault
time current curve transition, from pickup to the constant
delay bands, to improve coordination with downstream
devices.
Ground-fault pickup and ground-fault time delay
20
Trip Characteristics — MicroVersaTrip Plus™ and PM™ (cont.)
Short-Time Delay
Short-time delay is always provided when short-time
pickup is ordered. Short-time delay provides additional
refinement for coordination between upstream and
downstream protective devices. There are 3 time delay
bands that provide delays from 100msec to 350msec
corresponding to trip unit settings of 1 (MIN), 2 (INT)
3 (MAX).
Short time delay with I
2
t OUT
Selectable Short-Time I
2
t Function
Selectable short-time I
2
t is always provided with the short-
time option. The I
2
t allows the solid-state trip unit to better
coordinate with downstream thermal magnetic devices or
fuses. This function impacts the shape of short-time pickup
and short-time delay time current curves, and may be pro-
grammed either IN or OUT.
Short time delay with I
2
t IN
I
2
t
OUT
I
2
t
IN
I
2
t IN
Delay
Pickup
A
B
C
Ground Fault
Detection
Trip
t
t
t
Ground Fault
Detection
Ground Fault Curr ent
Ground-fault memory circuit

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE WavePro LVPCB and is the answer not in the manual?

GE WavePro LVPCB Specifications

General IconGeneral
BrandGE
ModelWavePro LVPCB
CategoryCircuit breakers
LanguageEnglish

Related product manuals