Installation 
(cont’d) 
DANGER 
HAZARDOUS VOLTAGE 
(Can Cause Severe Injury or Death) 
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components. 
Engine Start 
Control Connections 
The engine-start terminals are clearly identified by a 
label on the microcontroller backplate. In the case of 
manual transfer switches, or in other applications not 
requiring the microprocessor, clearly marked terminal 
blocks are provided in the upper left corner of the 
control panel for the engine start control wires. 
Transfer Switch. Figure 5 (pg.5) shows location of 
engine start connections for Automatic Transfer Switch. 
Terminals for field connections to the A3 Source 2 
auxiliary contacts and the A4 Normal auxiliary contacts 
are also provided. These terminals are clearly marked 
and appear on the side of the power panel. On 400 
amp metal frame units these terminals appear on 
the bracket above the operator handle. 
Initial Energization 
Before proceeding, refer to the information package 
supplied with the ATS and read and understand the 
information on all accessories provided. 
1.  Unlock the enclosure. 
2.  Open the enclosure. 
3.  Verify the correct system voltage. 
NOTE: The equipment rating nameplate on 
the transfer switch lists the voltage. 
See 
Figure 3
. 
4.  Close Source 1 circuit. breaker. 
NOTE:The controller will illuminate Source 1 
Available LED if proper voltage 
is sensed. 
5.  Verify the phase to phase voltages at Source 1 
line terminals. 
6.  Close Source 2 source circuit breaker. 
7.  Start the generator’s engine. 
NOTE
:  The controller will illuminate Source 2 
Available LED when preset voltage 
and frequency levels are reached. 
8.  Verify the phase to phase voltages at Source 1           
line terminals. 
9.  Verify that the phase rotation of Source 1 
is the same as the phase rotation of 
Source 2. 
10.  Shut down the generator’s engine. 
11.  Place the starting control in the Automatic position. 
12.  Complete the visual inspection of the transfer switch. 
13.  Close the enclosure. 
14.  Lock the enclosure. 
g 
GE Zenith Controls 
SERIAL NUMBER: 
RATING:  VOLTS -
HZ -
AMPS  -
PHASE -
SYSTEM VOLTS: 
MODEL NUMBER: 
Figure 3 
CAUTIONS 
Certain accessories, per specific 
schematics, can inhibit automatic transfer. 
Engine Gen-Set could start when 
engine control wires are attached. 
GE Zenith Controls 
ZTS / ZTSD Operation and Maintenance Manual (71R-3000) 
3