Therefrigerantsuctionedoutoftheevaporator(20)iscompressedbythe4cylindersoftheLPstage
(2)tointermediatepressureMP.Afterthat,thesuperheatedrefrigerantowsthroughtheintermediate
pressurechamber(3),whereitiscooledbytheliquidsubcoolersystemtoreducethedischargeend
temperature.The refrigerant then ows through the intermediate pressure line (4) to the electric
motor of the compressor for to cool the motor. After this, the refrigerant is suctioned in by the two HP
cylinders(5)andcompressedtothenalpressure.
Liquidsubcoolersystem
Theliquidsubcoolersystemconsistsofthecomponents
-liquidsubcooler(plateheatexchanger)(6)
-expansionvalve(7)
-sightglass(8)
-solenoidvalve(9)
-lterdrier(10)
Aftertherefrigerantreciever(15),theliquidlinewillbesplittedintotwolines:
Line A leads through the liquid subcooler (6) and the subcooled refrigerant ows to the
evaporator (20).Through Line B refrigerantis expanding throughthe expansion valve(7) into the
liquidsubcooler(6)inordertosubcooltherefrigerantoflineAandthroughtheintermediatepressure
line(MP)tocoolthesuperheatedrefrigerant,whichiscompressedfromlowpressuretointermediate
pressurechamber(3).
4| Description of functions

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GEA Bock HGZ7 Series and is the answer not in the manual?

GEA Bock HGZ7 Series Specifications

General IconGeneral
BrandGEA Bock
ModelHGZ7 Series
CategoryAir Compressor
LanguageEnglish

Related product manuals