EasyManua.ls Logo

gefran BDI50 Series

gefran BDI50 Series
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-76
11- 03
Carrier Frequency auto reduction due to temperature rise
Range
0
:Disable
1
:Enable
When inverter (heatsink) temperature rises above 80°C the Carrier Frequency is reduced by 4K.
When the temperature falls below less than 70°C, Carrier Frequency (PAR 11-01) is reset to
default.
Temperature can be displayed by setting parameter 12-00=04000.
70
80
t1
t2
T0
Temperature
Carrier
Frequency
10K
4K
t1
t2
T
0
11- 04
S-Curve Acc 1
11- 05
S-Curve Acc 2
11- 06
S-Curve Dec 3
11- 07
S-Curve Dec 4
Range
0.0 ~ 4.0
s
Use S Curve parameters where a smooth acceleration or deceleration action is required,
this will prevent possible damage to driven machines by sudden acceleration/deceleration.
S1
S2
S3
S4
RUN command
Actual
output
frequency
RUN
T
Note:
Regardless of the stall prevention period, actual acceleration and deceleration time =preset

Table of Contents

Related product manuals