3.3 Wiring Guidelines
3.3.1 Main considerations
1 Tightening Torque for Screw terminalsRefer to the tables 3-1, when using a
screwdriver or any other suitable tools to make connections.
2 Power terminals:
Single phase : L1 (L), L3 (N)
Three-phase 200V models: L1 (L), L2, L3 (N)
400V models: L1, L2, L3
3 For all cabling use copper wires and the cable size shall be according to the table
below rated at 40 degrees Celsius.
4 Power & Control cable Minimum rated voltage
240V AC system, 300V AC.
480V AC system, 600V AC.
5 Control cables should be separated from the power cables. Do not place them in the
same cable tray or cable trunking to prevent against electrical interference.
Table 3-1
Size
TM1
TM2
Cable Size
Tightening torque
Cable Size
Tightening torque
AWG
mm²
kgf.cm
Ibf.in
Nm
AWG
mm²
kgf.cm
Ibf.in
Nm
Size 1
22~10
0.34~6
14
12.15
1.37
24~12 0.5~2.5 4.08 3.54 0.4
Size 2
12.24
10.62
1.2
Size 3
18~8
0.82~8.4
18
15.58
1.76
24~12 0.5~2.5 5.1 4.43 0.5
Size 4
14~6
2~13.3
24.48
21.24
2.4
6 The maximum RMS symmetrical Current Ratings and voltage are listed as below:
Device Rating
Short circuit Rating Maximum Voltage
voltage
HP
220V 0.2~10 5000A 240V
440V 1~15 5000A 480V