What to do in case of a communication error during parameter transfer on a Gefran Inverter?
S
Shelley FisherSep 23, 2025
If you experience a communication error during the transfer of parameters from the drive to the memory of the keypad on your Gefran Inverter, recover a set of parameters from a compatible drive (model and size).
G
garciastevenAug 23, 2025
How to fix gefran ADL500 Inverter DC link overvoltage alarm?
E
Eric ScottAug 23, 2025
If your Gefran Inverter displays a DC link overvoltage alarm because the energy recovered from the voltage arriving at the drive power section is too high, you can extend the deceleration ramp. Alternatively, use a braking resistor connected to the specific terminals to dissipate the energy recuperation.
N
Nicholas WilliamsAug 25, 2025
What causes a motor overtemperature alarm on a gefran ADL500?
M
Meghan HarrisAug 26, 2025
A motor overtemperature alarm on your Gefran Inverter can be triggered by several factors:
* A load cycle that is too heavy.
* The motor being installed in an environment with a high ambient temperature.
* A faulty motor blower fan.
* Excessive load at slow speeds if the motor lacks a blower.
* Operating the motor below its rated frequency.
To address this, change the processing cycle or use a cooling fan to cool the motor.
E
Eric PenningtonAug 27, 2025
What to do if Gefran Inverter shows an overcurrent alarm?
S
Samantha MitchellAug 27, 2025
If your Gefran Inverter is showing an instantaneous overcurrent protection intervention alarm, it might be caused by incorrect settings of the current regulator parameters. You should check the current regulator parameters (menu 12.3) and inspect the wiring towards the motor.
C
Carrie RoweAug 27, 2025
How do I troubleshoot a ground fault alarm on a Gefran Inverter?
J
Jason WallaceAug 28, 2025
To troubleshoot a ground fault alarm (ground short circuit alarm) on your Gefran Inverter, check the drive and motor wiring. Also, ensure that the motor is not grounded.
J
Julia MarshallSep 18, 2025
What should I do if there is an error during loading of the parameter database on my gefran ADL500 Inverter?
C
Christina GillespieSep 18, 2025
If you encounter an error during loading of the parameter database saved in the Flash memory of the MDPLC application on your Gefran Inverter because the database saved is not valid, set the parameters to the desired value and run Save parameter.
S
shawnrichardsonSep 15, 2025
What to do if there is a safety function issue on a gefran ADL500?
T
Tyler RoseSep 15, 2025
If you encounter a safety function issue on your Gefran Inverter, switch the drive off and then back on. If the error persists, contact the technical service centre.
S
Shannon GoodmanSep 16, 2025
What if my gefran ADL500 displays a message during power card recognition?
J
Jose HigginsSep 17, 2025
If your Gefran Inverter displays a message during recognition of power cards, and it's not possible to drive the motor, it may be because the power card is configured for a drive that is incompatible with the regulation card, the configuration of the power card is not compatible with the regulation card, or the configuration required is not available on the power card. Download the correct configuration on the power card.
K
kmartinezSep 6, 2025
What does a speed reference loss alarm mean on a gefran ADL500?
M
Michael DownsSep 6, 2025
A speed reference loss alarm on your Gefran Inverter means the difference between the speed regulator reference and the actual motor speed is more than 100 rpm, usually because the drive is in the current limit condition. Check that the load is not excessive.
J
Justin CruzSep 3, 2025
How to resolve a braking resistor overload alarm on a Gefran Inverter?
B
Barbara WilsonSep 4, 2025
A braking resistor overload alarm on your Gefran Inverter means the current absorbed by the resistor is greater than the rated current. Check the size and condition of the braking resistor.
gefran ADL500 Specifications
General
Series
ADL500
Frequency Range
50/60Hz
Cooling Method
Forced Air Cooling
Input Voltage
380-480V
Output Voltage
0-480V
Power Range
0.75-500 kW
Control Method
V/F control, Sensorless vector control
Communication Protocols
Modbus RTU, CANopen
Protection Functions
Overcurrent, Overvoltage, Undervoltage, Overheating, Short circuit, Ground fault