Password protection function
Password protection function is available on all BDI50 models.
Range
0
: Enable all Functions
1
: Preset speeds 05- 01~05- 08 cannot be changed
2
: All Functions cannot be changed Except for preset speeds set in 05-
01~05- 08
3
: Disable All Function Except 13-06
Parameter 13-06 represents a first level of access control to parameters without any
password protection.
00000~65535
Parameter 13-07 allows to lock the access to all parameters. This parameter is only
available from Keypad.
When a parameter lock key number is entered in parameter 13-07. For any parameter
modification the key number has to be entered.
1. Parameter Lock Key Code STATUS
Parameter 13-07 can have the following STATUS:
13-07 = 00000 No password is set (Default is 00000 which means no Password)
13-07 = 00001 Password is set and waiting for confirmation but Lock function is disabled
13-07 = 00002 Password is confirmed and Lock function is enabled
2. Parameter Lock Key Code SETTINGS
2.1 The procedure to set a new password is the following (the new password for the
example is 12345):
The Parameter Lock Key Code STATUS become: 00001. User continue to have free
access to parameters depending on 13-06 parameter setting. To lock parameters,
password must be confirmed (see step 2.2)
When a new password is set, please use all precautions to recover it simply.
2.2 After step 2.1, the procedure to Lock the access to all parameters consists into
confirming the password: