6980415F_MSW_GFX4-IR_05-2019_ENG
634
R
Instrument state 4
bit
0 SSR Temperature sensor broken
1 SSR Temperature sensor over heat
2 phase_softstart_active
3 phase_softstart_end
4 frequency_warning or monophase_missing_line_warning
5 60Hz
6 short_circuit_current in phase softstart
7 over_peak_current in phase softstart
8 over_ms_current in normal operation
Table of instrument state 4
702
R
Voltage status
bit
0 frequency_warning
1 10% unbalanced_line_warning
2 20% unbalanced_line_warning
3 30% unbalanced_line_warning
4 rotation123_error
5 triphase_missing_line_error
6 60Hz
Table of voltage status