L
Lisa OrtegaAug 13, 2025
What to do if Gemu Control Unit valve leaks downstream?
- TtaylorbrianAug 13, 2025
If your Gemu Control Unit valve leaks downstream and doesn't close fully, it could be due to several reasons. The operating pressure might be too high; ensure it matches the data sheet specifications. Foreign matter could be lodged between the shut-off seal and seat; disassemble the actuator, remove any debris, and inspect the shut-off seal for damage, replacing it if needed. The valve body itself could be leaky or damaged, requiring inspection and potential replacement. A faulty shut-off seal can also cause leaks, so check it for damage and replace if necessary. Finally, a faulty actuator spring could be the culprit, necessitating actuator replacement.