General Information
Owner’s Manual for 60 Hz EcoGen™ Generator 7
Specifications
Generator
Engine
The specification sheet for this generator was included in
the documentation provided with the unit at the time of
purchase. For additional copies, consult your local
Independent Authorized Service Dealer.
Model 15 kW EcoGen
Rated Voltage 240
Rated Maximum Load
Current (Amps) at 240 Volts
(LP and NG)*
62.5
Main Circuit Breaker 65 Amp
Phase 1
Rated AC Frequency 60 Hz
Battery Requirement Group 26R, 12 Volts and 525 CCA Minimum (Generac Part No. 0H3421S)
Unit Weight in Lbs. (kilos) 536 (243)
Enclosure Aluminum
Normal Operating Range This unit is tested in accordance to UL 2200 standards with an operating
temperature of -20º F (-29º C) to 122º F (50º C). For areas where temperatures fall
below 32º F (0º C) a cold weather kit is recommended. When operated above 77º
F (25º C) there may be a decrease in engine power. Please reference the engine
specifications section.
These generators are rated in accordance with UL 2200, Safety Standard for Stationary Engine Generator
Assemblies, and CSA-C22.2 No. 100-04 Standard for Motors and Generators.
Model 15 kW EcoGen
Type of Engine GT-999
Number of Cylinders 2
Displacement 999 cc
Cylinder Block Aluminum w/Cast Iron Sleeve
Recommended Spark
Plug
RC12YC
Spark Plug Gap 0.040 in. (1.02 mm)
Starter 12 VDC
Oil Capacity Including
Filter
Approx. 3.75 Quarts / 3.55 Liters
Recommended Oil Filter Part #070185E
Recommended Air Filter Part #0J8478
Maximum wattage and current is subject to and limited by such factors as fuel BTU/joules content, ambient
temperature and altitude. Maximum power decreases about 3.5 percent for each 1,000 feet (304.8 meters) above
sea level, and also will decrease about 1 percent for each 10° F (6º C) above 60º F (15º C) ambient temperature.