Owners Manual
60 Hz Air-Cooled Generators
15 kW EcoGen™
SAVE THIS MANUAL FOR FUTURE REFERENCE
Para español , visita: http://www.generac.com/service-support/product-support-lookup
Pour le français, visiter : http://www.generac.com/service-support/product-support-lookup
000918
Register your Generac product at:
WWW.GENERAC.COM
1-888-GENERAC
(888-436-3722)
(000209a)
WARNING
This product is not intended to be used in
a critical life support application. Failure to
adhere to this warning could result in
death or serious injury.

Table of Contents

Other manuals for Generac Power Systems 15 kW EcoGen

Questions and Answers

  • B
    Benjamin PowellSep 4, 2025
    How to fix a Generac Power Systems Portable Generator that starts hard and runs rough?
    • M
      Matthew MaldonadoSep 4, 2025
      If your generator starts hard and runs rough, it could be due to: * A plugged or damaged air cleaner. Check or replace the air cleaner. * Defective spark plug(s). Clean, re-gap, or replace the spark plug(s). * Incorrect fuel regulator setting. Set the fuel regulator. * Incorrect fuel pressure. Confirm fuel pressure to regulator is 10–12 in. water column (19–22 mm mercury) for LP, and 3.5– 7 in. water column (9–13 mm mercury) for natural gas. * Fuel selector in the wrong position. Move the selector to the correct position.
  • D
    Dean Orozco Jr.Sep 18, 2025
    What causes no transfer to generator power after startup in Generac Power Systems 15 kW EcoGen?
    • M
      Margaret HicksSep 18, 2025
      If there's no transfer to generator power after startup with your Generac Power Systems Inverter, here are a couple of things to investigate: * The MLCB (generator disconnect) might be OFF (OPEN). Reset the generator disconnect to ON (CLOSED). * The engine may be warming up. Check the controller screen to verify the status.
  • K
    Kyle RodriguezSep 16, 2025
    Why Generac Power Systems 15 kW EcoGen Inverter unit consumes large amounts of oil?
    • S
      Samantha ColemanSep 16, 2025
      If your Generac Power Systems Inverter unit is consuming large amounts of oil, consider the following: * Excessive engine oil. Adjust the oil to the proper level. * Improper type or viscosity of oil. See Engine Oil Requirements. * Damaged gasket, seal, or hose. Check for oil leaks. * Restricted air filter. Replace the air filter.
  • N
    Natasha RodriguezSep 14, 2025
    How to troubleshoot no AC output from Generac Power Systems 15 kW EcoGen Inverter generator?
    • K
      Kevin BarreraSep 14, 2025
      If there's no AC output from your Generac Power Systems Inverter generator, try the following: * Check if the Main Line Circuit Breaker (MLCB), or generator disconnect, is OFF (OPEN). If so, reset the generator disconnect to ON (CLOSED). * Check the controller screen to verify status. The engine may be warming up.
  • A
    Amanda NormanSep 12, 2025
    Why Generac Power Systems 15 kW EcoGen Inverter engine starts hard and runs rough?
    • T
      Tonya HowardSep 12, 2025
      If your Generac Power Systems Inverter engine starts hard and runs roughly, possible causes include: * A plugged or damaged air cleaner. Check and clean the air cleaner. * Defective spark plug(s). Clean the spark plug(s), check the gap, and replace them if needed. * Incorrect fuel pressure. Confirm the fuel pressure to the regulator is 10–12 in water column (19–22 mm Hg) for LP, and 3.5–7.0 in water column (9–13 mm Hg) for natural gas. * The fuel selector is in the wrong position. Turn the fuel conversion valve to the correct position. * Valve(s) out of adjustment. Adjust the valve clearance.
  • M
    Mr. Brandon EdwardsSep 12, 2025
    What to do if Generac Power Systems 15 kW EcoGen engine cranks but will not start?
    • D
      Dr. Samantha Montgomery DDSSep 12, 2025
      If your Generac Power Systems Inverter engine cranks but doesn't start, consider these potential causes: * **No fuel:** Replenish the fuel supply and ensure the fuel valve is turned on. * **Defective spark plug(s):** Clean the spark plug(s), check the gap, and replace them if necessary. * **Valve clearance out of adjustment:** Reset the valve clearance. * **Fuel pressure too high:** Verify that the fuel pressure is at the correct level.
  • D
    davidfrancoSep 9, 2025
    How to fix Generac Power Systems 15 kW EcoGen Inverter when the engine will not crank?
    • A
      Amber DavisSep 9, 2025
      If your Generac Power Systems Inverter engine won't crank, here are a few things to check: * A blown fuse could be the issue. Replace the 7.5 amp fuse in the generator control panel, but if it keeps blowing, contact an Independent Authorized Service Dealer (IASD). * Loose, corroded, or defective battery cables can also prevent cranking. Tighten, clean, or replace them as needed. * A discharged battery may be the culprit. Try charging or replacing the battery.
  • S
    Shelly MarquezSep 7, 2025
    What to do if Generac Power Systems Portable Generator is set to OFF, but the engine continues to run?
    • L
      lblakeSep 7, 2025
      If the generator is set to OFF, but the engine continues to run, it may be caused by: * Control board wired incorrectly. Repair wiring or replace control board. * Defective control board. Replace control board.
  • T
    travisstevensonSep 5, 2025
    Why does my Generac Power Systems Portable Generator consume large amounts of oil?
    • J
      jared08Sep 5, 2025
      Excessive oil consumption in your generator can be attributed to: * The oil tank being overfilled. Adjust the oil to the proper level. * Damaged gasket, seal, or hose. Check for oil leaks.
  • S
    Sarah JonesAug 20, 2025
    What to do if my Generac Power Systems Inverter engine will not crank?
    • K
      Kevin ManningAug 21, 2025
      If your Generac Power Systems Inverter engine won't crank, it could be due to several reasons: * A blown fuse: Correct this by identifying and fixing the short circuit, then replace the 7.5 Amp fuse. * Loose, corroded, or defective battery cables: Tighten, clean, or replace the cables as needed. * A defective starter contact or motor: Tighten, clean, or replace these components as necessary. * A dead battery: Charge or replace the battery.

Summary

Section 1: Safety Rules & General Information

Read This Manual Thoroughly

Emphasizes understanding the manual for safe operation.

Safety Guidelines

Covers general safety rules, hazards, and warnings for operation and maintenance.

Section 3: Operation

Section 4: Maintenance

Scheduled Maintenance Overview

Importance and schedule for routine maintenance tasks.

Section 5: Troubleshooting; Diagnostics

Engine Troubleshooting

Common engine problems, causes, and solutions.

Generator Troubleshooting

Common generator problems, alarms, and solutions.

G-Flex Troubleshooting & Diagnostics

Troubleshooting specific G-Flex™™ alarms and diagnosing symptoms.

Generac Power Systems 15 kW EcoGen Specifications

General IconGeneral
Power Output15 kW
TypeStandby Generator
Automatic StartYes
Voltage120/240V
Frequency60 Hz
Dimensions48 x 25 x 29 inches
PhaseSingle
Engine TypeGenerac OHVI
Warranty5 years
Fuel TypeNatural Gas or Liquid Propane