45
EA21 EA31 EA42
Rated voltage 100 – 230V, 50/60 Hz
24V = /24V, 50/60 Hz
Rated voltage tolerance
+/- 10%
Rated output @ 24V AC/DC
@ 100 – 230V AC
22 VA
40 VA
32 VA
40 VA
40 VA
60 VA
Electric impedance 230V, 100kΩ
24V, 4.7kΩ
Altitude over NN (UL/CSA)
< 2000m
Protection class
IP 65 per EN 60529 *(3) UL/CSA: indoors use
Duty cycle 100% 50% 35%
Overload protection current/time-dependent (resetting) *(1)
temperature dependent
Electrical connections Connector plug 3 P+E per DIN EN 175301-03 (formerly
DIN 43650) Cable gland M20 x 1,5 according to ISO 724
Nominal torque Mdn
10 Nm 60 Nm 100 Nm
Actuating angle max. 180°, set to 90°
Control time 5 s / 90° at Mdn 15 s / 90° at Mdn 25 s / 90° at Mdn
Peak torque 20Nm 120 Nm 250 Nm
Ambient temperature -10° to + 50°C (2) -10° to + 50°C (2)
Allowable humidity max. 90% relative humidity, non condensing
Pollution grade (4) 2
Overvoltage category (4) II
Housing material PP breglass reinforced, ame retardant,external stainless
steel screws, non-losable
Position indication optical, integrated
Emergency manual override integrated
Flange pattern (5) F05 F07 F07
(1) Overload protection of the motor is dimensio-
ned so that the motor and the power supply board
are protected. As soon as the load is in the torque
range, the actuator runs again.
(2) For temperatures below -10°C as well as
condensation, the heating element no. 198 190
086 should be built in.
(3) Protection rating IP 67 for use of cable glands
and vertical installation
(4) Per EN 61010-1
(5) Per ISO 5211
6.3 Technical Specications