Appendix
0020200958_00 SUSTAIN ..r Installation and maintenance instructions 29
Status code Meaning
S.98 Automatic test programme: Return temperature sensor, heating demands blocked.
S.99 Internal automatic test programmes
S.108 Purging the combustion chamber, fan in operation
S.109 Product's standby mode activated
E Overview of fault codes
Fault code Meaning Possible cause
F.00 Fault: Flow temperature sensor NTC plug not plugged in or has come loose, multiple plug on the PCB not
plugged in correctly, interruption in cable harness, NTC sensor defective
F.01 Fault: Return temperature sensor NTC plug not plugged in or has come loose, multiple plug on the PCB not
plugged in correctly, interruption in cable harness, NTC sensor defective
F.10 Short circuit: Flow temperature sensor NTC sensor defective, short circuit in the cable harness, cable/casing
F.11 Short circuit: Return temperature sensor NTC sensor defective, short circuit in the cable harness, cable/casing
F.12 and
F.91
Short circuit: Cylinder temperature
sensor
NTC sensor defective, short circuit in the cable harness, cable/casing
F.13 Short circuit: Domestic hot water cylinder
temperature sensor
NTC sensor defective, short circuit in the cable harness, cable/casing
F.20 Safety switch-off: Overheating temperat-
ure reached
Incorrect earth connection between cable harness and product, flow or return
NTC defective (loose connection), black discharge via ignition cable, ignition
plug or ignition electrode
F.23 Safety switch-off: Temperature difference
too great (NTC1/NTC2)
Pump blocked, insufficient pump output, air in product, flow and return NTC
sensors connected the wrong way round
F.24 Safety switch-off: Temperature rise too
fast
Pump blocked, insufficient pump output, air in product, system pressure too
low, non-return valve blocked/incorrectly installed
F.25 Safety switch-off: Flue gas temperature
too high
Break in plug connection for optional flue gas safety temperature limiter
(STB), break in cable harness
F.27 Safety switch-off: Fault in flame detection Moisture on the electronics, electronics (flame monitor) defective, gas solen-
oid valve leaking
F.28 Fault: Ignition unsuccessful when starting
up
Gas meter defective or gas pressure monitor has triggered, air in gas, gas
flow pressure too low, thermal isolator device (TAE) has triggered, incorrect
gas restrictor, incorrect spare gas valve, fault on the gas valve, multiple plug
on PCB incorrectly plugged in, break in cable harness, ignition system (ig-
nition transformer, ignition cable, ignition plug, ignition electrode) defective,
ionisation current interrupted (cable, electrode), incorrect earthing of product,
electronics defective
F.29 Fault: Flame loss Gas supply temporarily stopped, flue gas recirculation, incorrect earthing of
product, ignition transformer has spark failure
F.32 Fan frost protection function active: Fan
speed outside the tolerance values
Plug on fan not correctly plugged in, multiple plug on PCB not correctly
plugged in, break in cable harness, fan blocked, Hall sensor defective, elec-
tronics defective
F.33 Fan frost protection function active: Air
pressure switch fault
Pressure monitor has not switched or has switched at a fan speed value that
is too high (insufficient air supply)
Pressure monitor plug not correctly plugged in, pressure monitor defective,
hose removed from between the pressure monitor and silencer, air/flue pipe
blocked
F.49 eBUS fault: Voltage too low Short circuit on eBUS, eBUS overload or two power supplies with different
polarities on the eBUS
F.61 Fault: Gas valve control system Short circuit/short to earth in cable harness for the gas valve, gas valve
defective (coils shorted to earth), electronics defective
F.62 Fault: Gas valve switch-off control Delayed switch-off of gas valve, delayed extinguishing of flame signal, gas
valve leaking, electronics defective
F.63 Fault: EEPROM Electronics defective
F.64 Fault: Electronics/sensor/analogue-to-
digital converter
Flow or return NTC short circuited, electronics defective
F.65 Fault: Electronics temperature too high Electronics overheating due to external influences, electronics defective