Furnace f ails to operate.
Integrated control module LED
display provides
error code.
Integrated control
module has lost
communications w ith
circulator blow er
motor.
Loose w iring connection
at circulator motor control
leads.
Failed circulator blower
motor.
Failed integrated control
module.
Furnace f ails to operate.
Integrated control module LED
display provides
error code.
Circulator blow er
motor horse power in
shared data set does
not match circulator
blow er motor horse
power.
Incorrect circulator blow er
motor in furnace.
Incorrect shared data set
in integrated control module.
Furnace operates at reduced
performance.
Airfow delivered is less than
expected.
Integrated control module LED
display provides
error code.
Circulator blow er
motor is operating in a
power, temperature,
or speed limiting
condition.
Blocked filters.
Restrictive ductw ork.
Undersiz ed ductw ork.
High ambient
temperatures.
Verif y circulator blower if motor
horse power is the same specif ed
for the specif c furnace mo del.
Replace if necessary.
Verif y shared data set is correct
for the specif c model. Re-populate
data using correct memory card if
required.
Turn power OFF prior to
repair
Replace motor w ith correct
replacement part.
Use memory card for the
specif c mo del
Insert memo ry card
BEFORE turning pow er ON.
Memo ry card may be
removed after data is loaded
and power is turned off.
Error code will be cleared
once shared data and mo tor
horse power match.
Check filters for blockage. Clean
filters or remove obstruction.
Check ductw ork for blockage.
Remove obstruction. Verify a
ll
registers are fully open.
Verif y ductwork is appropriately
sized for system. Resize/replace
ductwork if necessary.
See "III. Product Description" and
"IV. Location Requirements &
Considerations" furnace installation
requirements.
Turn power OFF prior to
repair.
Tighten or correct wiring
connection.
Check circulator blow er motor.
Replace if necessary.
Check integrated control module.
Replace if necessary.
Turn power OFF prior to
repair
Replace circulator mo tor
with correct replacement
part.
Replace integrated control
module w ith correct
replacement part.
Symptoms of Abnormal
Operation
Diagnostic /
Status LED
Codes
Possible CausesCorrective ActionsNotes & CautionsFault Description
TROUBLESHOOTING
50