SYSTEM OPERATION
9

The Airow quantity is displayed as a number on the three
7 segment displays, rounded to the nearest 100 CFM. The
display alternates airow amount and the system operating
status.
Each furnace has a “Maximum CFM” it is capable of
providing. All fan operations (Constant CFM, Cooling
Airow Proles, Low and High Stage gas heat airow,
outdoor Air Conditioner / Heat Pump Airow, etc.) are
based o󰀨 of multipliers which are percentages of this
maximum CFM. Max CFM is as follows:



Setup Furnace Airow: adjust the Gas Heating Airow
menu (gAF) setting to the desired percentage of maximum
airow. In most cases the default gas heat airow
will provide a temperature rise near the middle of the
acceptable range. High Stage CFM can be calculated
by the following equation: CFM = Max CFM * Selected
Heating Airow Percentage.
For Communicating Outdoor Units: Main airow adjustment
is not required. The Outdoor unit will determine the
appropriate amount of indoor airow to request. Airow
Trims can be made if desired.
For Non-Communicating outdoor units, determine the
proper airow (based o󰀨 tonnage of) the outdoor unit. Most
cooling systems are designed to work with airow between
350 and 450 CFM per ton. 400 CFM/TON is the industry
standard. Once desired airow has been determined, see
Tonnage / Airow table to identify the Tonnage Selection
that is closest to the desired airow. This table is based
on 400 CFM per ton where Airow = (400 CFM) x (Selected
Tonnage).


Enter the Tonnage (ton) menu either by using the on board
push buttons or phone application and select the Tonnage
Selection you identied.


Tonnage
Selection
Airflow
Tonnage
Selection
Airflow
Tonnage
Selection
Airflow
Tonnage
Selection
Airflow
1 400
2.3
920
3.6 1440
4.9
1960
1.1 440 2.4 960 3.7 1480 5 2000
1.2 480 2.5 1000 3.8 1520 5.1 2040
1.3 520 2.6 1040 3.9 1560 5.2 2080
1.4 560 2.7 1080 4 1600 5.3 2120
1.5 600 2.8 1120 4.1 1640 5.4 2160
1.6 640 2.9
1160
4.2 1680 5.5
2200
1.7 680 3 1200 4.3 1720 5.6 2240
1.8 720 3.1 1240 4.4 1760 5.7 2280
1.9 760 3.2 1280 4.5 1800 5.8 2320
2 800 3.3 1320 4.6 1840 5.9 2360
2.1 840 3.4 1360 4.7 1880 6 2400
2.2 880 3.5 1400 4.8 1920

The multi-circulator blower also o󰀨ers several custom
ON/ OFF ramping proles. These proles may be used to
enhance cooling performance and increase comfort level.
The ramping proles are selected using the Cooling Airow
Prole menu (if push buttons are used, use the CAP menu
to select the desired prole). Refer to the bullet points
below for a description of each ramping prole.
OFF
100% CFM 100% CFM
1 min
OFF
Figure 50
provides only an OFF delay of one (1) minute at 100% of the cooling demand Profile A(1)
50% CFM
1/2 min
100% CFM
100% CFM
1 min
OFF
OFF
Figure 51
ramps up to full cooling demand airflow by first stepping up to 50% of the full
demand for 30 seconds. The motor then ramps to 100% of the required airflow. A one (1)
minute OFF delay at 100% of the cooling airflow is provided.
Profile B(2)
100% CFM
OFF
OFF
ramps up to 85% of the full cooling demand airflow and operates there for
approximately 7 1/2 minutes. The motor then steps up to the full demand airflow. Profile C
also has a one (1) minute 100% OFF delay.
Profile C(3)
Figure 52
OFF
OFF
ramps up to 50% of the demand for 1/2 minute, then ramps to 85% of the full
cooling demand airflow and operates there for approximately 7 1/2 minutes. The motor
then steps up to the full demand airflow. Profile D has a 1/2 minute at 50% airflow OFF delay.
Profile D(4 or 5)
Figure 53
In general lower heating speeds will: reduce electrical
consumption, lower operating sound levels of the blower,
and increase the outlet air temperature delivered to the
home if heatmode is running. If cooling mode is running
the same airow adjustment will decrease the outlet air
temperature delivered to the home. The speeds available
allow the blower performance to be optimized for the
particular homeowner’s needs.