8
03 Product Introduction
User Manual V1.6-2024-03-20
No. Parts Description
8 BACK-UP
loads
• Connecting BACK-UP loads, such as loads requiring 24-hour power
supply or other important loads.
• Connecting unbalanced loads. L1, L2, L3 of the inverter respectively
connected to loads with dierent power.
• Loads with neutral wires are allowed when connecting three phase
loads to the BACK-UP port. Do not connect loads without neutral
wire to the BACK-UP port. Otherwise, the loads cannot work
properly or even be damaged.
• Do not connect auto-coupling or isolation transformers.
9 BACK-UP load
breaker
Self-prepared breaker. Recommended specications:
• GW15K-ET: nominal current≥32A, nominal voltage≥400V
• GW20K-ET: nominal current≥40A, nominal voltage≥400V
• GW25K-ET: nominal current≥50A, nominal voltage≥400V
• GW29.9K/30K-ET: nominal current≥63A, nominal voltage≥400V
10 Bypass switch To ensure the BACK-UP load is powered by the grid during the inverter
maintenance, install a bypass switch by yourself. Recommended
specications:
• GW15K-ET: nominal current≥32A, nominal voltage≥400V
• GW20K-ET: nominal current≥40A, nominal voltage≥400V
• GW25K-ET: nominal current≥50A, nominal voltage≥400V
• GW29.9K/30K-ET: nominal current≥63A, nominal voltage≥400V